Re: [foxboro] CP60 will not boot

  • From: "Boulay, Russ" <russ.boulay@xxxxxxxxxxxxxxxx>
  • To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
  • Date: Wed, 14 Sep 2005 11:16:18 -0400

On the AW perform a /opt/fox/bin/tools/fist AWLBUG

The AW should come back with a NSAP and Mac address.
NSAP in you case should be I00001 on a single node system.
There are times when the NSAP gets blown away....so AW won't connect to node
without it. 

Unless, you have other stations on the node running, you can try a to fist
one of them.

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of David Johnson
Sent: Wednesday, September 14, 2005 10:46 AM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] CP60 will not boot

Thanks to everyone, but no luck yet.

Terry,
        CP download is enabled.
Russ,
        copied to BBXXXXXX.UC  to DBXXXXXX.UC no luck
        copied DBXXXXXX.init to DBXXXXXX.UC no luck.
        put original DBXXXXXX.UC back.

        All of the files pointed to look OK.

Angel,
        looking for troubleshooting guide on TAC website.
        Haven't found it yet.


Here's a better description of the problem.
        AW51F is hosting this one CP only.
        DNBT connects AW51F to rack with only DNBT and CP60 in the rack.
        DNBT link light is green.
        DNBT NODEBUS light will flash one time when the CP is reset (or push

pulled) then no more on that side.
        DNBT TP Activity light flashes periodically (every 5 to 10 seconds)

        Everything was communicating and working yesterday when I rebooted
the AW, 
(waited for it to come back up, and online), then rebooted the CP60.  At 
that point I got stuck.  Letterbug is correct and appears to be correctly 
inserted, no bent pins.  The CP has successfully rebooted in this 
configuration about a week ago on a power outage.  I have not made any 
sysdef or image changes.

Any help would be appreciated.

Thanks,
David

        

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: