Bruno, If you used the DCM10e interface module to connect to the existing fieldb= us for your CP60 upgrade, this could be a symptom of a faulty fieldbus is= olator. I have seen instances where it affected only a certain FBM in the= rack.=20 If you have a spare fieldbus isolator, try changing the pair that serve t= his particular FBM, one bus at a time, and on the bus not currently being= used, of course. Shelby Jones Invensys =20 -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] = On Behalf Of Spenlehauert, Bruno Sent: Friday, January 26, 2007 1:37 AM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] FBM3 PIO communication error Hello all, We changed our system from V4.03 to V7.11 (including new CP60 processors)= and we have a recurrent FBM communication error: error occurs always on = the same FBM3 address POLDD3. Here is a copy of the smon_log: 2007-01-25 13:43:58 CP004E Equip =3D CP004E SYSMON -00056 Currently using= PIO bus A 2007-01-25 13:43:58 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus = Access Error on B 2007-01-25 13:44:26 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus = Access Recovery on B 2007-01-25 13:56:46 CP004E Equip =3D CP004E SYSMON -00057 Currently using= PIO bus B 2007-01-25 13:56:46 CP004E Equip =3D POLDD3 SYSMON -00068 Single PIO Bus = Access Error on A 2007-01-25 13:57:44 CP004E Equip =3D POLDD3 SYSMON -00070 Single PIO Bus = Access Recovery on A 2007-01-25 15:09:16 CP004E Equip =3D CP004E SYSMON -00056 Currently using= PIO bus A 2007-01-25 15:09:18 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus = Access Error on B 2007-01-25 15:09:30 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus = Access Recovery on B We tried to: 1)=09Make an EEprom update=20 2)=09Change the FBM 3)=09Move the FBM in another place 4)=09Change the FBM head 5)=09Unwire all the signals coming to the board Problem keep the same: does anybody know how to fix the problem?=20 Thank you in advance. SPENLEHAUERT Bruno bruno.spenlehauert@xxxxxxxxxxxxxxxxxxxxx Maintenance Polym=C3=A8re P=C3=B4le Europ=C3=A9en de D=C3=A9veloppement=20 F-54810 LONGLAVILLE Phone 03 82 44 80 44 / Fax 03 82 44 80 85 =20 ----------------------------------------- Disclaimer: This e-mail communication and any attachments may contain confidential and privileged information and is for use by the designated addressee(s) named above only. If you are not the intended addressee, you are hereby notified that you have received this communication in error and that any use or reproduction of this email or its contents is strictly prohibited and may be unlawful. If you have received this communication in error, please notify us immediately by replying to this message and deleting it from your computer. Thank you. =20 =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html =20 foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave =20 Confidentiality Notice: =0AThe information contained in this electronic m= essage and any attachment(s) to this message are intended for the exclusi= ve use of the recipient(s) and may contain confidential, privileged or pr= oprietary information. If you are not the intended recipient, please noti= fy the sender immediately, delete all copies of this message and any atta= chment(s). Any other use of the E-Mail by you is prohibited.=0A =0AConfidentiality Notice: =0AThe information contained in this electroni= c message and any attachment(s) to this message are intended for the excl= usive use of the recipient(s) and may contain confidential, privileged or= proprietary information. If you are not the intended recipient, please n= otify the sender immediately, delete all copies of this message and any a= ttachment(s). Any other use of the E-Mail by you is prohibited.=0A _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave