We've also had faulty mounting structures, have you got empty slots in = the mounting structure? If you have move the FBM to the empty slot to = test. If not try swapping FBM and nose cone with an FBM in another slot = and see if the problem remains or moves to the other slot. If it remains = on the same slot, the only thing left is changing the Mounting = structure. Rgds, Dirk Pauwels - DCS/MOC coordinator=20 Engineering dept. Hexion Specialty Chemicals E mail: dirk.pauwels@xxxxxxxxxx T. +32.(0)3.570.95.97 F. +32.(0)3.570.16.09 Mob. +32.(0)497.428.300 -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] = On Behalf Of Spenlehauert, Bruno Sent: vrijdag 26 januari 2007 7:37 To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] FBM3 PIO communication error Hello all, We changed our system from V4.03 to V7.11 (including new CP60 = processors) and we have a recurrent FBM communication error: error = occurs always on the same FBM3 address POLDD3. Here is a copy of the smon_log: 2007-01-25 13:43:58 CP004E Equip =3D CP004E SYSMON -00056 Currently = using PIO bus A 2007-01-25 13:43:58 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus = Access Error on B 2007-01-25 13:44:26 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus = Access Recovery on B 2007-01-25 13:56:46 CP004E Equip =3D CP004E SYSMON -00057 Currently = using PIO bus B 2007-01-25 13:56:46 CP004E Equip =3D POLDD3 SYSMON -00068 Single PIO Bus = Access Error on A 2007-01-25 13:57:44 CP004E Equip =3D POLDD3 SYSMON -00070 Single PIO Bus = Access Recovery on A 2007-01-25 15:09:16 CP004E Equip =3D CP004E SYSMON -00056 Currently = using PIO bus A 2007-01-25 15:09:18 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus = Access Error on B 2007-01-25 15:09:30 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus = Access Recovery on B We tried to: 1) Make an EEprom update=20 2) Change the FBM 3) Move the FBM in another place 4) Change the FBM head 5) Unwire all the signals coming to the board Problem keep the same: does anybody know how to fix the problem?=20 Thank you in advance. SPENLEHAUERT Bruno bruno.spenlehauert@xxxxxxxxxxxxxxxxxxxxx Maintenance Polym=E8re P=F4le Europ=E9en de D=E9veloppement=20 F-54810 LONGLAVILLE Phone 03 82 44 80 44 / Fax 03 82 44 80 85 =20 ----------------------------------------- Disclaimer: This e-mail communication and any attachments may contain confidential and privileged information and is for use by the designated addressee(s) named above only. If you are not the intended addressee, you are hereby notified that you have received this communication in error and that any use or reproduction of this email or its contents is strictly prohibited and may be unlawful. If you have received this communication in error, please notify us immediately by replying to this message and deleting it from your computer. Thank you. =20 =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html =20 foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: = mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: = mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave