Re: [foxboro] FBM3 PIO communication error

  • From: "Landry, Scott" <scott.landry@xxxxxxxxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Fri, 26 Jan 2007 02:30:27 -0500

  Change the letterbug with known good ones ?

  Bent or pushed in pins ?

  Can you correlate the smon messeges with the trended=20
  CP004E_STA:STATION.PIOEGB   You could use this to see if
  That particular FBM in giving Good to Bad transitions.=20
 =20
  What is the current EEprom level and Software level on POLDD3
  Are there other FBM03 working on CP004E.

  I forget now at what FBM level/CP Image you need MPOLL=3D0 on 10/30/40.
  MPOLL is unused on 60.

  Did you try deleting the ECB and re creating it. Changing execution ord=
er?

 =20

  Regards,


   Ben There

 =20


 =20
 =20

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] =
On Behalf Of Spenlehauert, Bruno
Sent: Friday, January 26, 2007 12:37 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] FBM3 PIO communication error

Hello all,

We changed our system from V4.03 to V7.11 (including new CP60 processors)=
 and we have a recurrent FBM communication error: error occurs always on =
the same FBM3 address POLDD3.
Here is a copy of the smon_log:

2007-01-25 13:43:58 CP004E Equip =3D CP004E SYSMON -00056 Currently using=
 PIO bus A
2007-01-25 13:43:58 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus =
Access Error on B
2007-01-25 13:44:26 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus =
Access Recovery on B
2007-01-25 13:56:46 CP004E Equip =3D CP004E SYSMON -00057 Currently using=
 PIO bus B
2007-01-25 13:56:46 CP004E Equip =3D POLDD3 SYSMON -00068 Single PIO Bus =
Access Error on A
2007-01-25 13:57:44 CP004E Equip =3D POLDD3 SYSMON -00070 Single PIO Bus =
Access Recovery on A
2007-01-25 15:09:16 CP004E Equip =3D CP004E SYSMON -00056 Currently using=
 PIO bus A
2007-01-25 15:09:18 CP004E Equip =3D POLDD3 SYSMON -00069 Single PIO Bus =
Access Error on B
2007-01-25 15:09:30 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus =
Access Recovery on B


We tried to:

1)=09Make an EEprom update=20
2)=09Change the FBM
3)=09Move the FBM in another place
4)=09Change the FBM head
5)=09Unwire all the signals coming to the board

Problem keep the same: does anybody know how to fix the problem?=20

Thank you in advance.

SPENLEHAUERT Bruno
bruno.spenlehauert@xxxxxxxxxxxxxxxxxxxxx
Maintenance Polym=C3=A8re
P=C3=B4le Europ=C3=A9en de D=C3=A9veloppement=20
F-54810 LONGLAVILLE
Phone 03 82 44 80 44 / Fax  03 82 44 80 85
=20




-----------------------------------------
Disclaimer:

This e-mail communication and any attachments may contain confidential
and privileged information and is for use by the designated
addressee(s) named above only. If you are not the intended addressee,
you are hereby notified that you have received this communication in
error and that any use or reproduction of this email or its contents is
strictly prohibited and may be unlawful. If you have received this
communication in error, please notify us immediately by replying to
this message and deleting it from your computer.

Thank you.
=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20



Confidentiality Notice: =0AThe information contained in this electronic m=
essage and any attachment(s) to this message are intended for the exclusi=
ve use of the recipient(s) and may contain confidential, privileged or pr=
oprietary information. If you are not the intended recipient, please noti=
fy the sender immediately, delete all copies of this message and any atta=
chment(s). Any other use of the E-Mail by you is prohibited.=0A

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: