Re: [foxboro] CP270 with FBM100's

  • From: William C Ricker <wcricker@xxxxxxxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Fri, 23 Sep 2016 00:05:30 -0400

Forgot to include that FBI100 or 200 can be used to extend that maximum length 
to 6000 ft. 

WCR

Sent from my iPhone

On Sep 23, 2016, at 12:03 AM, William C Ricker <wcricker@xxxxxxxxxxxxxxx> 
wrote:

Fieldbus length when connected to FCP270 is shorter than when connected to 
CP40. Now it's 3200 ft. 
It had been 4000 I believe. Length OK?

WCR

Sent from my iPhone

On Sep 22, 2016, at 10:59 PM, Brian Long <blong@xxxxxxx> wrote:

Just replaced a CP40B with CP270 connected to FBM100’s.  Have not had any
FBM or A/B fieldbus issues prior to change.  Now getting intermittent A
errors on random FBM’s.  We’ve done this same CP upgrade a number of times
without issue.  We’ve changed the FBI modules and nosecones on A,
re-terminated twinax cables, etc.  Not having much luck, any words of
wisdom?


Thanks,

Brian



_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave


 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: