Looking into this topic myself. How many CADs can one run from a single 
WP/AW? Can it be more than the number of DMs/FVs?

Thanks,
Corey
 



From:
"Johnson, Alex P (IOM)" <Alex.Johnson@xxxxxxxxxxxx>
To:
"foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
Date:
10/14/2011 01:21 PM
Subject:
Re: [foxboro] Alarm management
Sent by:
foxboro-bounce@xxxxxxxxxxxxx



First Problem - If the contents of the file are identical, you can use a 
Solaris link (ln -s <file> <linedFile>) or a Windows shortcut and name the 
file after the CB.AlarmType. This is a bit of a maintenance effort, but...

You could also maintain that association (CBP to file name) in a file and 
have your script search the association file (grep) for the file name to 
display. This is much better, but requires a bit more script work. I'd go 
this way.


Second Problem - The most common thing is to run two CADs on the WP and 
use a filter to segregate the displayed messages. It works well.

Regards,
 
Alex Johnson
Invensys Operations Management
10900 Equity Drive
Houston, TX 77041
+1 713 329 8472 (desk)
+1 713 329 1600 (operator)
+1 713 329 1944 (SSC Fax)
+1 713 329 1700 (Central Fax)
alex.johnson@xxxxxxxxxxxx







 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: