Re: [foxboro] Alarm management

  • From: Jeremy Milum <jmilum@xxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Fri, 14 Oct 2011 14:44:38 -0400

On Fri, Oct 14, 2011 at 11:59 AM,  <dirk.pauwels@xxxxxxxxxx> wrote:
> In the new approach they won't be considered as alarms anymore, Therefore
> they're not supposed to appear on the alarm page,  but we still need some
> way of informing the operator these items need some attention.
> Does anyone uses something like this and how did you configure it?

I used a single CAD, but configured three new buttons: "Alarms"
(Priority 1-3 for me), "Messages" (Priority 4 & 5), "All" (Priority
1-5).

The "Alarms" buttons loads a filter for alarms matching Pri 1-3, the
"Messages" button loads a filter to match Pri 4-5, and the "All"
button unloads all filters.


-- 
Jeremy
 
 