-----Original Message----- From: Johnson, Alex P (IPS) Sent: Wednesday, May 23, 2007 12:19 AM The relative picks in some of the faceplates have been configured with action names. For example, the OUT relative pick on the PID faceplates have the name .OUT. If you call in a PID detail display and issue the command pref dmcmd "protect name .OUT" the relative pick for the .OUT parameter is no longer pickable. -----Original Message----- If a protected element is not "pickable", it would still be "changeable" by other means, correct? For example, if a display has user-defined up/down buttons that change the .OUT parameter without a pick, then the above protection method would not work. Some considerable thought needs to be invested when designing and building a display if selected (not global) protection is (or may) be desired. Brad Wilson brad.wilson@xxxxxxxxxxxxxxxx Invensys Systems, Inc 1090 King Georges Post Rd, Suite 204 Edison, NJ 08837 732-874-0087 Confidentiality Notice: The information contained in this electronic message and any attachment(s) = to this message are intended for the exclusive use of the recipient(s) and = may contain confidential, privileged or proprietary information. If you are= not the intended recipient, please notify the sender immediately, delete a= ll copies of this message and any attachment(s). Any other use of the E-Mai= l by you is prohibited. _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave