Re: [foxboro] FV Display Call Up Time HP Gen9

  • From: Dirk Pauwels <dirk.pauwels@xxxxxxxxxx>
  • To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
  • Date: Wed, 6 Jul 2016 09:13:34 +0000

Maybe you can try to RDP to this station or use tight vnc or something similar 
to find out if it's related to the video cards...
Since it occurs on all stations maybe it's related to a setting on the video 
cards?
I suppose when you open a certain display multiple times and the problem stays 
it's not related to optimization.

Rgds,

Dirk
-----Oorspronkelijk bericht-----
Van: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] Namens ;
Brian Long
Verzonden: dinsdag 5 juli 2016 23:47
Aan: foxboro@xxxxxxxxxxxxx
Onderwerp: Re: [foxboro] FV Display Call Up Time HP Gen9

Truthfully don't think this is the issue because we've called displays multiple 
times, sometimes ok, sometimes not.  Also occurs when brining up select screens.

Also have the flicker issue on busy displays which we thought was a long solved 
problem.


Brian



Sent from my iPhone

On Jul 5, 2016, at 4:24 PM, Boulay, Russ <Russ.Boulay@xxxxxxxxxxxxxxxxxxxxxx> 
wrote:

If displays were just moved, they hold the optimization of the former 
workstation info.
So it may take 3 callups to clear.
First callup needs to flush previous optimizations and relearn
differences Second callup should optimize fully learned paths
Subsequent callups good If convert fdf to g ....then copy and convert
g to fdf....all optimization is cleared and displays should optimize in 2 
callups.
Find all connections the first callup...
then good all subsequent callups.


-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of Brian Long
Sent: Tuesday, July 05, 2016 2:17 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] FV Display Call Up Time HP Gen9

Displays were just moved not converted.  Do we need to covert all to g and 
then back to fdf?

Thanks,
Brian

Sent from my iPhone

On Jul 5, 2016, at 3:40 PM, Boulay, Russ 
<Russ.Boulay@xxxxxxxxxxxxxxxxxxxxxx> wrote:

How were the displays moved to the new workstation?

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of Bergeron, Normand
Sent: Tuesday, July 05, 2016 1:37 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] FV Display Call Up Time HP Gen9

Hi Brian,
Check your /usr/fox/customer/hi/dmcfg file.  Are your DM's configured as 
operator or view only? If configured as view only, Foxview might be slow 
even if the environment is set to Eng_env....

Norm


_____________________________________________________________________
_
_______________

Normand Bergeron | Schneider Electric | North America Operations |
Canada | Spécialiste d'application / Application specialist
Phone: +1 514 421 4210 | Fax: +1 514 421 8054 | Mobile: +1 514 220
5081
Email: normand.bergeron@xxxxxxxxxxxxxxxxxxxxxx | Site:
www.schneider-electric.com | Address: 4, rue Lake, H9B 3H9
Dollard-des-Ormeaux, Quebec, Canada

*** Please consider the environment before printing this e-mail

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx
[mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of Brian Long
Sent: Tuesday, July 5, 2016 4:32 PM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] FV Display Call Up Time HP Gen9

We’ve just completed upgrading from Dell Server 2003 to HP Gen9 Server 2008. 
 FV is very slow in calling up displays, sometimes it’s fine, have not taken 
the time to put a call in yet but will.  Anyone have any helpful 
suggestions?  We had no issues with DellR710 with Win2003.  We have 11 
servers, all 11 have this issue.


Thanks in advance,

Brian Long

Arkansas Kraft





________________________________
Lawter Notice: The information (including any attachments) contained in this 
communication is confidential, private and proprietary, may be privileged or 
otherwise protected by applicable law or legal rule, and is intended only for 
the use of the addressee(s). Unauthorized use, disclosure, distribution or 
copying is strictly prohibited and may be unlawful. If you have received this 
communication in error, please notify the sender immediately by reply e-mail, 
or by calling the sender, and then delete it completely from your system.
 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: