Re: [foxboro] Priority in Alarm messages

  • From: <tom.vandewater@xxxxxxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Fri, 19 Jan 2007 14:44:54 -0500

        First off, the following disclaimer.  The following can only be
counted on if you are using a UNIX based Legacy Foxboro alarm historian
but may be true in other configurations.  The alarm priority is
obviously passed to the alarm historian but is filtered out of the
printer output.  You can follow the results of my telnet session below
which dumps the contents of the file
/usr/hstorian/almhist
which is a flat text(data)file that stores alarm messages.  Notice the
(4LOABS) in the first alarm.  The 4 just before LOABS is the alarm
priority.  In my research of 3rd party alarm packages some of them
access the almhist file directly as a database for their own
manipulations which you can also do;<)

04AW01# /usr/bin/strings /usr/hstorian/almhist |more
C0904:FI24008.C10                       5566 COMPRESSOR   OIL FLOW
4LOABS
01-15 23:32:33     69.97 GPM    (    70.00) OIL TO 5566 LO FLOW
ALM
C0904:FI24008.C10                       5566 COMPRESSOR   OIL FLOW
0LOABS

Cheers,
Tom VandeWater
Control Systems Developer/Analyst
Dow Corning Corp.
Carrollton, KY  USA

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]
On Behalf Of Corey R Clingo
Sent: Friday, January 19, 2007 1:19 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] Priority in Alarm messages

Hmm...I didn't know that the priority did not come out on the printer.
Not=20
really sure why this would be the case, as the Alarm Manager and  legacy

historian know about it.  Is this true of any non-AM alarm device?


To do long-term alarm logging, I have some scripts to read and parse the

almhist file that the legacy historian uses for a circular alarm history

buffer.  These were based on some code I found on the Cassandra site and

in some Foxboro HH documents, but I've had to modify them several times
as=20
I've come across weird data the historian puts in this file for certain=20
alarm types, and to add additional features (like putting the year in
the=20
timestamp).  It's not real-time (it runs out of cron every hour), but=20
suits my needs.  I hope to get this into some kind of database (either
my=20
own or some alarm-management product's) for better analysis
capabilities.


As for how the alarm management vendors determine priority, most of the=20
packages I've seen also import part or all of the system configuration=20
(either periodically from iccprt dumps or live via OPC) and get the=20
priorities from that.


Corey Clingo
BASF Corporation






"Ghodhbani, Hafedh" <Hafedh.Ghodhbani@xxxxxxxxxxxx>=20
Sent by: foxboro-bounce@xxxxxxxxxxxxx
01/19/2007 04:32 AM
Please respond to
foxboro@xxxxxxxxxxxxx


To
<foxboro@xxxxxxxxxxxxx>
cc

Subject
[foxboro] Priority in Alarm messages







Hello,
We are sending plant alarms continuously to a PC for analysis.
We would like to add the alarm priority to the alarm message text.
Can you please advise how to proceed.

For your information, this is the alarm message we want to modify the
structure:

PK2103:PC21103.PK2103                   HP N2 PURGE GAS
LOABS
01-19-07 09:35:45:2     0.05BAR        ( 0.05) LOW ALARMS
ALM

Regards
Lead C&I Eng
BG Group
Tel:+21674259250  ex 574



______________________________________________________________________
BG Energy Holdings Limited
Registered in England & Wales No: 3763515
Registered address:
100 Thames Valley Park Drive
Reading, Berkshire RG6 1PT  UK
Telephone: +44 (0)118 935 3222
Website: http://www.BG-Group.com

This e-mail is intended only for the addressee named above.  As this
e-mail may contain confidential or privileged information, please
advise us immediately if you are not the named addressee or the person
responsible for delivering the message to the named addressee.  The
contents should not be disclosed to any other person nor copies taken.




=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: