Re: [foxboro] Integrator 30 Style B failing (P0961BD-0E)

  • From: "Kevin Fitzgerrell" <fitzgerrell@xxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Sun, 9 Mar 2008 09:43:24 +0900

Kashif,

Sounds good.

When this station fails, does it leave a dump file?
/usr/fox/sysmgm/softmgr/dump

What is the eeprom revision of the integrator in smdh?

Regards,

Kevin FitzGerrell


On Sat, Mar 8, 2008 at 9:24 PM, Kashif Ijaz <kashifijaz93@xxxxxxxxxxx> wrote:
> There were 7 compounds in this station having MDSCAN block. I have increased 
> the period from 1 sec to 2 sec and staggered the phases to reduce the I/O 
> SCAN from 78% to 39%. Will continue to observe the effects.
>
>  Regards,
>
>  Kashif Ijaz
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process