Re: [foxboro] AIM*OPC Server CLOSE_WAIT errors

  • From: Ted Jirik <ted.jirik@xxxxxxxxxxxxxxx>
  • To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
  • Date: Thu, 14 Mar 2013 10:57:41 -0700

David,

Also be sure there is nothing in the AIM* Servers field in the opc server 
configurator / server parameters (advanced) tab

Ted

On Mar 14, 2013, at 10:37 AM, Ted Jirik <ted.jirik@xxxxxxxxxxxxxxx> wrote:

> David,
> 
> Just spoke to our field service rep and he verified my thinking. That is what 
> we did to solve it at two sites.
> 
> Reboot after changes?
> 
> Be sure other servers are not listed in your an_init.tcp file?
> 
> Ted
> 
> On Mar 14, 2013, at 8:48 AM, "Johnson, David" 
> <David.Johnson@xxxxxxxxxxxxxxxxxx> wrote:
> 
>> Ted,
>> 
>> That sounds like a potential problem, but we checked, and the disable 
>> broadcast box was checked in APIAdmin on ALL of the AWs listed.  We only 
>> have AIM*OPC Server on SRVONE, there are no other OPC servers or clients on 
>> the DCS network.  So I still don't know why the AIM*OPC Server is attempting 
>> to talk to the other AWs.  And although I only listed 2 sample netstat lines 
>> with the CLOSE_WAIT there are many, possibly hundreds, to each AW after a 
>> few days.
>> 
>> Any other ideas?
>> Thanks,
>> David
>> 
>> 
>> 
>> -----Original Message-----
>> From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On 
>> Behalf Of Ted Jirik
>> Sent: Thursday, March 14, 2013 9:32 AM
>> To: foxboro@xxxxxxxxxxxxx
>> Subject: Re: [foxboro] AIM*OPC Server CLOSE_WAIT errors
>> 
>> David,
>> 
>> We had the same problem. As I recall we had to disable broadcast requests 
>> under edit server connection in apiadmin. We did this on all stations and 
>> the problem went away.
>> 
>> Ted 
>> 
>> On Mar 14, 2013, at 6:25 AM, Johnson, David wrote:
>> 
>>> Hello All,
>>> We have an AIM*OPC server installed on an AW running Win 2003 Server. The 
>>> OPC server is working (will return data, no errors).  We have an OSI PI 
>>> data collector running.  It will connect to and get data from I/A via the 
>>> OPC link.  This will work for several days, but then the AW becomes so 
>>> unresponsive, it must be rebooted.  After a reboot the problem goes away 
>>> for a day or two, and then returns.
>>> 
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: