Re: [foxboro] just a tip

  • From: "Wiggins, Bryan" <Bryan.Wiggins@xxxxxxxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Tue, 18 May 2004 14:34:47 -0600

The is a SCI for ain blocks that does not look at the 1 st  3/4 % flow.  =
This works with flow and square root functions.  If everything in the =
field is correct  I would choose the sci of 7 for a 4 to 20 MA signal.

-----Original Message-----
From: Jaime Claramunt R. (Inforsa) [mailto:jclaramunt@xxxxxxxxxxxxxxx]
Sent: Tuesday, May 18, 2004 2:28 PM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] just a tip


hey list,

does anybody have a tip for this ...
we have some flowmeters (AIN) that still indicates some when there is no
flow...
this is used then in ACCUM blocks, and I want to find the way to =
indicate
this block to accumulate only values over a low limit...with limits ?
clamping ? (without hold ...)

thanks

jaime Claramunt
INFORSA Paper Mill

=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: