Re: [foxboro] iccdrvrtsk upload error

  • From: Sascha Wildner <swildner@xxxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Tue, 07 Mar 2006 16:20:32 +0100

Sascha Wildner wrote:
> steve.shimp@xxxxxxxxxxxxxx wrote:
> 
>>I am getting the following error when trying to automate a CP upload with
>>the iccdrvrtsk:
>>"ICCupload error class = 20 error = 112 text = ICCupload: error -30 on
>>upload all"
> 
> 
> And damn right it is :) because you probably don't have a compound 
> called 'all'. Error -30 is EQEMPTY ("Change queue is empty", see 
> /usr/include/fox/om_ecode.h).
> 
> iccdrvr.tsk documentation (B0193NE) will tell you that the UPLOAD 
> command will only work on a block or a compound but not on a CP.
> 
> Known bug, I don't think it will ever be fixed. No, wait! It's 
> documented, hence it's a feature. :)
> 

Oops, sorry for the noise. :)

In fact, the documentation says just typing "upload" should be enough to 
upload all compounds in the station. Did you type "upload all" or "upload"?

-- 
Sascha Wildner
erpicon Software Development GmbH
Neusser Str. 724-726
50737 Köln
Germany

Phone: +49 221 9746069
Fax:   +49 221 9746099
eMail: swildner@xxxxxxxxxx
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: