Sascha Wildner wrote: > steve.shimp@xxxxxxxxxxxxxx wrote: > >>I am getting the following error when trying to automate a CP upload with >>the iccdrvrtsk: >>"ICCupload error class = 20 error = 112 text = ICCupload: error -30 on >>upload all" > > > And damn right it is :) because you probably don't have a compound > called 'all'. Error -30 is EQEMPTY ("Change queue is empty", see > /usr/include/fox/om_ecode.h). > > iccdrvr.tsk documentation (B0193NE) will tell you that the UPLOAD > command will only work on a block or a compound but not on a CP. > > Known bug, I don't think it will ever be fixed. No, wait! It's > documented, hence it's a feature. :) > Oops, sorry for the noise. :) In fact, the documentation says just typing "upload" should be enough to upload all compounds in the station. Did you type "upload all" or "upload"? -- Sascha Wildner erpicon Software Development GmbH Neusser Str. 724-726 50737 Köln Germany Phone: +49 221 9746069 Fax: +49 221 9746099 eMail: swildner@xxxxxxxxxx _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave