Re: [foxboro] ICCopen error while downloading

  • From: RAKESH DASH <rakeshinxs@xxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Sat, 26 Mar 2016 00:52:09 +0530

Hi Tom,
I cant see the CP+ in locks folder.
I get the error even while downloading standard blocks.
Rgds,
Rakesh Dash
Rakesh,
Although not the same error message, it sounds similar to the ICC already
open problem we run into at times with IACC.  Check usr\fox\sp\locks and
look for a file cpname+ (plus sign on end).  If there, delete it and try
again.

Does this problem only exist when downloading your Modbus device ECBs and
DCI blocks or do you get the same error when downloading any standard block?
Tom Badura
Plastics Engineering Company

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of RAKESH DASH
Sent: Friday, March 25, 2016 12:01 AM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] ICCopen error while downloading

Anyone out there who has faced similar issue and can suggest. I m still
stuck.
Rgds,
Rakesh
On Mar 11, 2016 11:20 PM, "RAKESH DASH" <rakeshinxs@xxxxxxxxx> wrote:

Hi,
I have a modbus device which I added. Added few analog points as well.
But now when I try to download the controller in IACC I am getting an
error as ICCopen error: icConnectVp : icCpConnect problem.
Can anyone help ? I cant afford to reboot the processor as Plant is
running.

Rgds,
Rakesh





_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave




_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave


 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: