Hi Tom, Have a seat while I vent. We went down this path ourselves recently, and found out some interesting things. =3D> The HHT50 ONLY works in a lab environment with Foxcom transmitters. It won't work if the transmitter is connected to an intelligent FBM, such as an FBM18/FBM43/FBM243. We didn't try it with HART. This one item is our biggest heartache. =3D> You can't import anything from the old HHT/PC20 platforms. =3D> You only have support for the newer I/A series transmitters - if = you have older 800 series transmitters, your are, how they say, SOL. I put in a product enhancement request (PER) to add this support, but even if it existed, the other drawbacks of the HHT50 make it near useless for us. =3D> There is no upgrade path to a field configuration device (for = Foxcom anyway) of any sort. The old HHT and PC20 software are it.=20 =3D> There is a really cool "Inkball" game on the HHT50 that is it's = only redeeming feature. I would encourage anyone in the same boat that will be attending the Users Conference in Boston this month to bring this up (discuss, whine, complain - whatever you want to call it) with the Foxboro M&I folks there. There is a real need for some device/software to replace the old PC20/HHT. And by replace, I mean incorporate the same functionality. Good luck, Gaylon Hicks TVA - Browns Ferry -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of tommcd6217@xxxxxxxxxxx Sent: Wednesday, July 04, 2007 5:27 AM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] Foxboro HHT50 We have recently purchased 2 HHT50's for use with our Foxcom and Rosemont transmitters. We seem to have problem communicating with both so far kinda iffy. We run about 800 Foxboro transmitters and 300 Rosemonts. Field communication seems to be iffy and shop use is somewhat more reliable. I've read the PACTware manual and have not figured out how to import a file database of our transmitter/configurations. Has anyone tried to do this or am I looking at lot of typing/time? Any help/shortcuts/explanations would be greatly appreciated as we are starting to deplete our original old, patched, non-repairable, simple HHT's Tom McDonald Valero Inc. Power Control Technician Delaware City, Delaware 302-836-6740 =20 =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html =20 foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: = mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: = mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave