Loyd, Please refer to the attached notes from B0193AC. Since only each input pair is non isolated with next pair, if we connect CS of alternate pairs then all the four channels will be non isolated. -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx]On Behalf Of Loyd Greer Sent: Tuesday, January 20, 2004 2:43 PM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] FBM09C Hello, =20 I would like to know if there would be a problem connecting the 2 CS = terminals together, on a common input pair, on an FBM09C ? I've checked = it out to see that it works. I just don't want to cause any long term = problems.=20 Loyd Greer Great Lakes Chemical=20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave -- No attachments (even text) are allowed -- -- Type: application/msword -- File: FBM9c rules.doc _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave