Re: [foxboro] WinNT V6.4 time change DST *****With AIMAT V3.2*****

  • From: "Boulay, Russ" <Russ.Boulay@xxxxxxxxxxxxxxxxxxxxxx>
  • To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
  • Date: Tue, 17 Nov 2015 07:57:34 -0500

The folder named is not on standard IA. It is part of a custom application from
one of Invensys Application groups.

For the version of IA you are running, to tie GPS to Mesh, you need the GPS
hardware kit of antenna, mtk modem, and time card that installs into the AW.
And then properly configure in sysdef

Sent from my iPhone

On Nov 17, 2015, at 1:30 AM, Hariharan Srinivasan
<Hariharan.Srinivasan@xxxxxxxxx> wrote:

I have Windows XP & IA 8.4.2.
I am not able to identify the folder named (foxind\NTPTimeSync\data\)

Kindly suggest how to sync through MESH network.

With regards,
Hariharan.S

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Joseph M. Riccardi
Sent: 11 November 2015 23:24
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] WinNT V6.4 time change DST *****With AIMAT V3.2*****

BINGO!!! This is exactly what I needed. Thanks Scott, and the others that
sent documentation we did not have...


Joseph M. Riccardi
386-451-7607 Cell

Joe@xxxxxxxxxxxxx

"To give real service you must add something that cannot be bought or
measured with money; and that is sincerity and integrity." - Donald A. Adams

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Landry, Scott
Sent: Wednesday, November 11, 2015 6:15 AM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] WinNT V6.4 time change DST *****With AIMAT V3.2*****



Joe,

3. Configure the time server for the NTP software The file
d:\opt\foxind\NTPTimeSync\data\ntp.conf must be modified to contain the IP
address of the NTP server. This file has a default entry of "server
127.127.0.1".
Only the IP address 127.127.0.1 should be edited.
Then copy the ntp.conf to the c:\winnt\system32\drivers\etc directory.

6. Reboot the AW.

Regards,


Scott

________________________________________
From: foxboro-bounce@xxxxxxxxxxxxx [foxboro-bounce@xxxxxxxxxxxxx] On Behalf
Of Joseph M. Riccardi [Joe@xxxxxxxxxxxxx]
Sent: Tuesday, November 10, 2015 3:24 PM
To: foxboro@xxxxxxxxxxxxx
Subject: Re: [foxboro] WinNT V6.4 time change DST *****With AIMAT V3.2*****

Well, I have come full circle back to Scott's info... I have searched your
GCS site for the NTP TimeSync User Guide referenced and I get every User
Guide but this one. Where did you get the copy you quoted from below? At
this point all I really need is the location of the NTP TimeSync file that
contains the server name or the IP address it is looking to sync with. I
find out that corporate server IP address has changed.

Anyone have a copy of that User Guide or know the location of the info I need?

Thanks


Joseph M. Riccardi
386-451-7607 Cell

Joe@xxxxxxxxxxxxx

"To give real service you must add something that cannot be bought or
measured with money; and that is sincerity and integrity." - Donald A. Adams





_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave




_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave



______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
______________________________________________________________________

*** Confidentiality Notice: This e-mail, including any associated or attached
files, is intended solely for the individual or entity to which it is
addressed. This e-mail is confidential and may well also be legally privileged.
If you have received it in error, you are on notice of its status. Please
notify the sender immediately by reply e-mail and then delete this message from
your system. Please do not copy it or use it for any purposes, or disclose its
contents to any other person.


_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave


Other related posts: