Re: [foxboro] AOUT Issue

  • From: "Prakash I.G." <prakashig.2011@xxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Fri, 22 Jan 2016 19:33:45 +0530

Hi
We had faced same problem in Hart Modules. Need to upgrade firmware.
Prakash G
On 21 Jan 2016 9:53 pm, "Brian Long" <blong@xxxxxxx> wrote:

We had an AOUT  block go into HOLD for some unknown reason, caused us some
down time.  No matter what was tried (in SELECT) block would not come out
of HOLD, nothing addressed to it, no SEQ code, etc.   Going to ICC and
doing a DONE fixed, did not have to do DELETE/UNDELETE.  This was not new
config, no system changes or updates were done.  This is a CP270 lightly
loaded.


Anyone else seen anything like this before?  This actually has us very
concerned.



Thanks in advance,

Brian Long




_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave





 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: