Martin, The .pulldown files still work under windows. Just be sure to use right syntax. in /usr/fox/config edit the .pulldown file. Standard it is looking like this; Control_Cfg -p 100 Display_Build -p 100 Display_Cfg -p 100 DispAlarmCfg -p 100 DspConventions -p 100 Font_Edit -p 100 FoxDraw -p 100 FoxPanelsCfg -p 100 Historian -p 100 ...... The right mouse button click can be protected via the /opt/customer/env/disp_eng.mnu file; COMMAND -label "Open with FoxDraw" -cmd "run \opt\fox\wp\FoxDraw\foxdraw $SELDISP -fvname $DMNAME" -p 100,101 SEPARATOR COMMAND -label "Moveable" -cmd "ov_switch -move" -enable stat COMMAND -label "Stationary" -cmd "ov_switch -stat" -enable move SEPARATOR COMMAND -label "Close" -cmd "close" Simply modify the -p acces level values. FoxDraw can not be run in read only mode. Regards, Martijn Daamen FAS Engineer Invensys Netherlands ________________________________ From: "martin.theobald@xxxxxxxxx" <martin.theobald@xxxxxxxxx> To: foxboro@xxxxxxxxxxxxx Sent: Thursday, 28 February 2013, 13:08 Subject: [foxboro] Protecting FoxView Environments using '.pulldown' Files Alex & Co., Well I gave it a try and then involved GCS. The net result is that currently, in FoxView, we cannot use '.pulldown' files to protect access to Environments like we can with Display Manager. GCS have suggested that we raise a PER if we want this feature to be considered for a future release. Regards, Martin Theobald ------------------------------------------------- Martin Theobald eControl - Runcorn INEOS Chlor Vinyls M: +44 7767 87 1989 T: +44 1928 51 2044 F: +44 1928 51 6653 ------------------------------------------------- From: "Johnson, Alex P (IOM)" <Alex.Johnson@xxxxxxxxxxxx> To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>, Date: 08/02/2013 15:22 Subject: Re: [foxboro] PASSWORD FOR FOXDRAW CHANGES Sent by: foxboro-bounce@xxxxxxxxxxxxx I don't know. I've never tried it. Regards, Alex Johnson Invensys Operations Management 10900 Equity Drive Houston, TX 77041 +1 713 329 8472 (desk) +1 713 329 1600 (operator) +1 713 329 1700 (Central Fax) alex.johnson@xxxxxxxxxxxx -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of martin.theobald@xxxxxxxxx Sent: Friday, February 08, 2013 9:03 AM Cc: 'foxboro@xxxxxxxxxxxxx'; foxboro-bounce@xxxxxxxxxxxxx Subject: Re: [foxboro] PASSWORD FOR FOXDRAW CHANGES Alex, I should really try this but I'll ask instead, on MS Windows boxes, can you make use of a '.pulldown' file in the directory that holds the environment files for FoxView? The idea would be to prevent some environments from being selected from others. Regards, Martin Theobald ------------------------------------------------- eControl - Runcorn INEOS Chlor Vinyls M: +44 7767 87 1989 T: +44 1928 51 2044 F: +44 1928 51 6653 ------------------------------------------------- _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave