Ashley, What revision are your problem CP60s and FCMs? Have you got ferrites installed on the CP60s? Have you followed Foxboro's guidelines regarding the CP60 DIN rail (isolation, single high quality ground, only approved equipt. on the rail, etc)? At my last plant, the combination of ferrites, DIN rail isolation and grounding + 1.16 firmware finally took care of our PIO bus errors. Regards, Kevin FitzGerrell On 4/13/07, aad@xxxxxxxxxxxxx <aad@xxxxxxxxxxxxx> wrote: > Good Day > > I have an installation - AW70 - XP with Foxboro Version 7.0 with CP60's > and FCM10ef's. > We are experiencing excessive PIO bus errors from four of the CP's > > I have implemented the recommendations of the "SA2005064I - QF1007465b" > and all FCM's are on software revision 1.16. > > I have monitored the PIOE1R, PIOEFT, PIOEGB parameters using the > "all-pio-read" and "all-pio-reset" scripts and have not recoreded any > errors on the problematic CP's. > > The System Monitor still records messages with PIO bus falures and errors > for these CP's. > Sample of SYSMON log: > > 2007-04-11 11:41:17 OSCP06 Equip = P06121 SYSMON -00068 Single PIO Bus > Access Error on A > 2007-04-11 11:41:17 OSCP06 Equip = P06122 SYSMON -00068 Single PIO Bus > Access Error on A > 2007-04-11 11:41:40 OSCP06 Equip = P06224 SYSMON -00068 Single PIO Bus > Access Error on A > 2007-04-11 11:42:00 OSCP06 Equip = P06100 SYSMON -00172 FCM A module Failed > 2007-04-11 11:42:01 OSCP06 Equip = P06115 SYSMON -00068 Single PIO Bus > Access Error on A > 2007-04-11 11:42:01 OSCP06 Equip = P06100 SYSMON -00193 FCM A no longer > failed > 2007-04-11 11:42:01 OSCP06 Equip = P06121 SYSMON -00070 Single PIO Bus > Access Recovery on A > 2007-04-11 11:42:01 OSCP06 Equip = P06122 SYSMON -00070 Single PIO Bus > Access Recovery on A > 2007-04-11 11:42:25 OSCP06 Equip = P06224 SYSMON -00070 Single PIO Bus > Access Recovery on A > 2007-04-11 11:42:42 OSCP06 Equip = P06115 SYSMON -00070 Single PIO Bus > Access Recovery on A > 2007-04-11 11:43:16 OSCP06 Equip = P06200 SYSMON -00172 FCM A module Failed > 2007-04-11 11:43:16 OSCP06 Equip = P06231 SYSMON -00068 Single PIO Bus > Access Error on A > 2007-04-11 11:43:16 OSCP06 Equip = P06200 SYSMON -00193 FCM A no longer > failed > 2007-04-11 11:44:02 OSCP06 Equip = P06231 SYSMON -00070 Single PIO Bus > Access Recovery on A > > > What am I not getting? > What is the System Monitor monitoring? > What else can I look at? > > Any ideas and help would be appreciated. > > Thanks > > Ashley Davey > Protea Automation Solutions(Pty) Ltd > Johannesburg > South Africa > > > > > ------------------------------------------- > South Africas premier free email service - www.webmail.co.za > ------------------------------------------------------------------ > For super low premiums, click here http://www.webmail.co.za/dd.pwm > > > > _______________________________________________________________________ > This mailing list is neither sponsored nor endorsed by Invensys Process > Systems (formerly The Foxboro Company). Use the info you obtain here at > your own risks. Read http://www.thecassandraproject.org/disclaimer.html > > foxboro mailing list: //www.freelists.org/list/foxboro > to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join > to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave > > _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave