Dimitris,
That error usually occurs when you the workstation is set to DONE or PCHANG in
SysDef before reinstalling I/A, instead of NOTYET which allows you to reinstall
I/A.
Thanks,
Philip Pulas
Lead Engineer, Process Systems
Tesoro Martinez Refinery
Ph: (925) 372-3043
Email: philip.g.pulas@xxxxxxxxxxx
-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On ;
Behalf Of Dimitris Legakis
Sent: Thursday, September 29, 2016 2:39 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro]
Hello list,
One question for you:
Trying to reinstall IA series 7 to a new foxboro P92 workstation, a strange
error appeared in the log file that did not alow us to continue. the error was
saying:
"Unable to start NuTcracker service"
"Unable to start NuTcrackerkernel service"
Does anyone have a clue about this? Any suggestions?
Thank you in advance.
Dimitris
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html
foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html
foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave