Brian,
We use a â€œCALCA” just above the ACCUM block.
The Bit that â€œClears” the ACCUM block is a BI01 on the CALCA. It is used in
the logic to create snapshots of the ACCUM block just before it clears.

The key is that the CALCA block be above the ACCUM block in the ICC (or
first in execution order in the Galaxy).

If you need details of the logic let me know.

Regards,

On Wed, May 26, 2021 at 9:07 AM Long, Brian <blong@xxxxxxx> wrote:

Wanting a clever/clean way to save ACCUM.OUT value right before a reset.
We do this quite often and our solution works well and without issue but
it's clunky.  Wondered if there's a simple / clean way to do that we've not
thought of.
Thanks,
Brian




_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subjectÿin
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subjectþave


--
Michael Jaudon Sent from iPhone

 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: