Re: [foxboro] Foxboro SPEC200 system migration and connectivity

  • From: "Johnson, Alex P (IOM)" <Alex.Johnson@xxxxxxxxxxxx>
  • To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
  • Date: Wed, 8 Sep 2010 11:05:47 -0500

If it is really SPEC200, it is an analog control system and therefore:

1) There is no information located in the system unless you are referring to 
the wiring.
2) There is no information to extract except for the cards used and how they 
are interconnected.
3) There is no location for information inside the system
4) There are no backups
5) There is no readable format

We did offer SPEC200 migration cards. See PSS 21H-7R1B3, but I believe that 
they are in Mature (or Lifetime) now. These cards plugged into the SPEC 200 
slots and preserved the wiring, but move the control to the controller.

If what you have is INTERSPEC - SPEC 200 with special cards for computer 
communication, we offered an INTERSPEC integrator - see PSS 21H-7G1B3. This 
module presented SPEC 200 data on the Nodebus. I believe that this is also in 
Mature or Lifetime.

If what you have is really a SPECTRUM system, the answers are much more 
complicated. There are a variety of controllers and I/O modules and supervising 
computers and workstations.


All of this information is available from our Client Sales Executive. Tell me 
where you are and I'll arrange for someone to call.


Regards,
 
Alex Johnson
Invensys Operations Management
10900 Equity Drive
Houston, TX 77041
+1 713 329 8472 (desk)
+1 713 329 1600 (operator)
+1 713 329 1944 (SSC Fax)
+1 713 329 1700 (Central Fax)
alex.johnson@xxxxxxxxxxxx (current)
alex.johnson@xxxxxxxxxxxxxxxx (good until September 2010)


Attend OpsManage'10
Real Collaboration. Real-Time Results.

Click Here to learn more about these events and to register.




-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On 
Behalf Of bhaskar shetty
Sent: Tuesday, September 07, 2010 11:59 PM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] Foxboro SPEC200 system migration and connectivity

Hi,
How to migrate the Foxboro SPEC200 system to the latest DCS system either to
Foxboro or some other competitor? Please share all the information you have.
We are looking for options to migrate this system. Even we plan to consider
the third-party vendors.
What are all the information needs to be extracted from the spec200 system?
Where this information is located inside the system?
How to take the backup?
How to convert into readable format?
Is there anyway that we can connect this system to the latest Foxboro system
?
Please share the experience if you had already done.
Thanks in Advance,
Regards,
Bhaskar


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 


*** Confidentiality Notice: This e-mail, including any associated or attached 
files, is intended solely for the individual or entity to which it is 
addressed. This e-mail is confidential and may well also be legally privileged. 
If you have received it in error, you are on notice of its status. Please 
notify the sender immediately by reply e-mail and then delete this message from 
your system. Please do not copy it or use it for any purposes, or disclose its 
contents to any other person. This email comes from a division of the Invensys 
Group, owned by Invensys plc, which is a company registered in England and 
Wales with its registered office at 3rd Floor, 40 Grosvenor Place, London, SW1X 
7AW (Registered number 166023). For a list of European legal entities within 
the Invensys Group, please go to 
http://www.invensys.com/legal/default.asp?top_nav_id=77&nav_id=80&prev_id=77.

You may contact Invensys plc on +44 (0)20 3155 1200 or e-mail 
reception@xxxxxxxxxxxxx This e-mail and any attachments thereto may be subject 
to the terms of any agreements between Invensys (and/or its subsidiaries and 
affiliates) and the recipient (and/or its subsidiaries and affiliates).


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: