Thanks for the pointer, but reading the docs raises other questions.  They
say that the max value is 8192K, yet I have several totalizers wih .OUT
values that go to 9 digits.  I checked out the faceplate, and it does
reference the .OUT parameter, but uses formatting to get 10 places plus a
decimal place.  Does this mean that every digit after 7 is bogus?

Corey



|---------+---------------------------->
|         |           steve.shimp@exxon|
|         |           mobil.com        |
|         |           Sent by:         |
|         |           foxboro-bounce@fr|
|         |           eelists.org      |
|         |                            |
|         |                            |
|         |           06/03/2002 03:20 |
|         |           PM               |
|         |           Please respond to|
|         |           foxboro          |
|         |                            |
|---------+---------------------------->
  
>-------------------------------------------------------------------------------------------------------------------------------|
  |                                                                             
                                                  |
  |               To:  foxboro                                                  
                                                  |
  |        cc:                                                                  
                                                  |
  |        Subject: Re: [foxboro] ACCUM block OUT parameter and omget           
                                                  |
  
>-------------------------------------------------------------------------------------------------------------------------------|






Corey,

According to B0193AX, Rev. K, "... the block saves the running accumulator
in extended precision format to minimize truncation errors.  However, the
block stores the output (OUT) as a single precision float of 7-digit
resolution with a maximum value of 8,192,000 (8192 K) and a
user-specifiable range."

I was just reviewing the specs of the ACCUM block for a small project I'm
involved with.

Steve Shimp
Senior Systems Analyst
ExxonMobil Paulsboro Lube Plant
Phone:  856-224-5059
Cell:  609-820-8501
Fax:  856-224-5030
Email:  steve.shimp@xxxxxxxxxxxxxx




 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: