> Help somebody! Is it time for dial-a-prayer (TAC)? Have you tried using the Pref command to see what is in the panel? Se B0700AP-Alarm Management Commands and try the prtalmpnl command. Pref -{am_name} ascmd "prtalmpnl /usr/fox/alarms/almpanel.txt" This will let you know what is actually loaded. (print command) Also, there is a command to load the panel.(loadalmpnl) Try reducing the list(say to one point) and adding them into the panel. Print out to see it actually took it, and add more into the list when successful.Repeat this and you should be able to narrow down the culprit point(s). Ronald G. Schafer Distrubuted Controls System Administrator White Birch Paper Bear Island L.L.C. Division 10026 Old Ridge Rd. Ashland Va. 23005 804-227-4034 Email: rschafer@xxxxxxxxxxxxxxxxxxxxxx -- No attachments (even text) are allowed -- -- Type: text/x-vcard -- File: rschafer@xxxxxxxxxxxxxxxxxxxxxxxxxx -- Desc: rschafer@xxxxxxxxxxxxxxxxxxxxxxxxxx _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave