Hello all,=0D=0A =0D=0AWe changed our system from V4=2E03 to V7=2E11 (inclu=
ding new CP60 processors) and we have a recurrent FBM communication error: =
error occurs always on the same FBM3 address POLDD3=2E=0D=0A=0D=0AHere is a=
 copy of the smon_log:=0D=0A=0D=0A2007-01-25 13:43:58 CP004E Equip =3D CP00=
4E SYSMON -00056 Currently using PIO bus A=0D=0A2007-01-25 13:43:58 CP004E =
Equip =3D POLDD3 SYSMON -00069 Single PIO Bus Access Error on B=0D=0A2007-0=
1-25 13:44:26 CP004E Equip =3D POLDD3 SYSMON -00071 Single PIO Bus Access R=
ecovery on B=0D=0A2007-01-25 13:56:46 CP004E Equip =3D CP004E SYSMON -00057=
 Currently using PIO bus B=0D=0A2007-01-25 13:56:46 CP004E Equip =3D POLDD3=
 SYSMON -00068 Single PIO Bus Access Error on A=0D=0A2007-01-25 13:57:44 CP=
004E Equip =3D POLDD3 SYSMON -00070 Single PIO Bus Access Recovery on A=0D=
=0A2007-01-25 15:09:16 CP004E Equip =3D CP004E SYSMON -00056 Currently usin=
g PIO bus A=0D=0A2007-01-25 15:09:18 CP004E Equip =3D POLDD3 SYSMON -00069 =
Single PIO Bus Access Error on B=0D=0A2007-01-25 15:09:30 CP004E Equip =3D =
POLDD3 SYSMON -00071 Single PIO Bus Access Recovery on B=0D=0A=0D=0AWe trie=
d to:=0D=0A=0D=0A1)       Make an EEprom update =0D=0A2)       Change the F=
BM=0D=0A3)       Move the FBM in another place=0D=0A4)       Change the FBM=
 head=0D=0A5)       Unwire all the signals coming to the board=0D=0A=0D=0AP=
roblem keep the same: does anybody know how to fix the problem? =0D=0A=0D=
=0A Thank you in advance=2E=0D=0A=0D=0A =0D=0A=0D=0A=0D=0A=0D=0ASPENLEHAUER=
T Bruno=0D=0Abruno=2Espenlehauert@performancefibers=2Ecom=0D=0AMaintenance =
Polym=E8re=0D=0AP=F4le Europ=E9en de D=E9veloppement =0D=0AF-54810 LONGLAVI=
LLE FRANCE=0D=0APhone +33 82 44 80 44 / Fax  +33 82 44 80 85=0D=0A =0D=0A=
=0D=0A-----------------------------------------=0D=0ADisclaimer:=0D=0A=0D=
=0AThis e-mail communication and any attachments may contain confidential=
=0D=0Aand privileged information and is for use by the designated=0D=0Aaddr=
essee(s) named above only=2E If you are not the intended addressee,=0D=0Ayo=
u are hereby notified that you have received this communication in=0D=0Aerr=
or and that any use or reproduction of this email or its contents is=0D=0As=
trictly prohibited and may be unlawful=2E If you have received this=0D=0Aco=
mmunication in error, please notify us immediately by replying to=0D=0Athis=
 message and deleting it from your computer=2E=0D=0A=0D=0AThank you=2E=0D=
=0A
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: