[foxboro] CLAN to ATS ...., again

  • From: Glen <gbounds@xxxxxxxxxxxxx>
  • To: foxboro@xxxxxxxxxxxxx
  • Date: Tue, 28 Mar 2006 15:24:25 -0500

I just wanted to bring this up again since I am trying to replace my
CLAN modules with this new "fangled" ATS modules and mesh
network.

*History:*

I have a "simple" two-node IA system with two AW51C's on each
node.

I have a P92 "AWXP" running OPC station software 7.x.

*Problem:

*You can't use the OPC AW to host the ATS modules as we were
lead to believe.  You have to add a real AW70 (P91 or P92) to
host the ATS's.

I just wanted everyone else to know this before they ordered ATS
modules and switches.  As usual, I had to learn it the hard way.

Glen

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts:

  • » [foxboro] CLAN to ATS ...., again