Content-Type: text/plain; charset="us-ascii" Content-Transfer-Encoding: quoted-printable Has anyone seen a case where the hardware annunciator silences itself automatically? We have a pair of p92's installed at version 8.3 in one particular area of our plant and cag'd together and certain alarms silence the horns on both stations after sounding for a seemingly random amount of time (5 to 45 seconds). I cant find anything in common that points me in the right direction. =20 It does silence the horns on both stations. =20 I have checked the init.user file and the HRN_OPT is still commented so it should be default(manual only), and ACK_HORN =3DY (commented out, default also). Also, the init.user is the same file we use on the rest of our stations and this problem doesn't happen anywhere else. =20 Not all alarms cause this behavior, but there don't seem to be anything in common. =20 Ronald G. Schafer Distrubuted Controls System Administrator White Birch Paper Bear Island L.L.C. Division 10026 Old Ridge Rd. Ashland Va. 23005 804-227-4034 Email: rschafer@xxxxxxxxxxxxxxxxxxxxxx =20 =20 =20 -- No attachments (even text) are allowed -- -- Type: text/x-vcard -- File: rschafer@xxxxxxxxxxxxxxxxxxxxxxxxxx -- Desc: rschafer@xxxxxxxxxxxxxxxxxxxxxxxxxx _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave