I think all that last step is doing is running the program "/opt/aim/bin/histstart &" that runs on boot-up. As long as AIMAPI is up, you should be able to just run "/opt/aim/bin/histstart &" from the command line. I have never tried this though. Also, you should be able to run the AIM*Histmgr program from your PC in the Windows environment without having to log in to the AW51. It comes with the AIM*Utilities option on the client CD. You need an an_init.cfg file on the PC that tells the PC which IP address that the second Ethernet port on the AW51 is using. As far as GoGlobal, you should seriously investigate replacing GoGlobal with VNC. You can find it free at http://www.realvnc.com/download.html. VNC provides a true OpenWindows desktop as opposed to the "screen wipe" that GoGlobal gives you. This overcomes many of the limitations that GoGlobal has in terms of running all the "remote draw" applications in I/A. Also, upgrades to GoGlobal are no longer being provided by Invensys. There is a bit of a learning curve involved in setting up VNC, but I have some documents I can provide off-line that should get you started. Tim Lowell Control Systems Engineer ConocoPhillips Trainer Refinery (610) 364-8362 tim.c.lowell@xxxxxxxxxxxxxxxxxx -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of michael_bovenkamp@xxxxxxxxxx Sent: Thursday, February 17, 2005 10:06 AM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] Starting an AIM Historian Instance through VT100 Hello List, I would like some advice regarding starting an AIM Historian Instance through a VT100 unix command instead of using the historian manager graphical user interface. I use helpful hint HH1001 "Restarting AIMHistorian" from TAC often to stop and restart my AIM*Historian processes without rebooting an AW51D box. I use a thin-client "go-global" when working remotely. Unfortunately, I'm unable to perform the last step "open histmanager and turn the instance on" without opening the histmanager graphical user interface. If I open the gui through either the vt100 /opt/aim/bin/histmgr command or the config menu selection, the gui pops up on the AW in front of the operator instead of the goglobal thin client screen that I'm using. Thank you for any help. AIM Historian 3.2 I/A 6.3 AW51D Regards, Michael Bovenkamp Control Systems Engineering Engineering Maintenance and Technology Dofasco Inc. Phone: (905) 548-7402 Fax: (905) 548-4269 =20 _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave