Re: [foxboro] Default Alarm Historian in Alarm Manager

  • From: "Den Haese, Patrick" <phaese@xxxxxxxxxxx>
  • To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
  • Date: Tue, 15 Jan 2002 14:52:12 -0500

You will have to edit the /usr/fox/wp/bin/mk_glbls file,
and look for HSTNAME=$HIST . Change $hist in the historian name you want.
Patrick Den Haese
Senior System Service Engineer
Invensys Systems N.V./S.A.
phaese@xxxxxxxxxxx  - Belgium


                -----Original Message-----
                From:   Lowell, Tim: [mailto:tlowell@xxxxxxxx]
                Sent:   Tuesday, January 15, 2002 16:38
                To:     'foxboro@xxxxxxxxxxxxx'
                Subject:        [foxboro] Default Alarm Historian in Alarm
Manager


                We have FoxView and AIM*AT 3.02 at our site.  When a    WP
gets rebooted, or
                the Alarm Manager gets restarted for some reason, the Alarm
Historian name
                must be selected from the "Historian" button on the Alarm
History Display
                (AHD).  For the "Historian" button to work, you must have an
access level of
                zero.  We have recently decided to lock out the Console
Supervisors from any
                access level zero functions. This means if a WP reboots in
the middle of the
                night or on the weekends, the console guys have no access to
the AHD until
                someone in the Control Group comes in and resets it for
them.

                My question is, is their any way to tell the AHD what the
default historian
                name is?  I know I can change the "Historian" button to work
on a different
                access level, which would solve the nights/weekends problem,
but I'd prefer
                to go a step further and just tell the AHD what the correct
Historian name
                is on boot-up, since we only have one Historian anyway.  Has
anyone solved
                this problem?

                Tim Lowell
                Control Systems Engineer
                Phillips Petroleum Company, Trainer Refinery
                Phone:  610-364-8362
                Fax:    610-364-8211
                tlowell@xxxxxxxx
                 
                 
        
___________________________________________________________________
                This list is neither sponsored nor endorsed by The Foxboro
Company.
                Use the information obtained here at your own risk. For
disclaimer,
                see
http://www.thecassandraproject.org/disclaimer.html#maillist

                list info:   //www.freelists.org/list/foxboro
                subscribe:
mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
                unsubscribe:
mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 
 
___________________________________________________________________
This list is neither sponsored nor endorsed by The Foxboro Company.
Use the information obtained here at your own risk. For disclaimer,
see http://www.thecassandraproject.org/disclaimer.html#maillist

list info:   //www.freelists.org/list/foxboro
subscribe:   mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave

Other related posts:

  • » Re: [foxboro] Default Alarm Historian in Alarm Manager