Re: [foxboro] Default Alarm Historian in Alarm Manager
- From: "Den Haese, Patrick" <phaese@xxxxxxxxxxx>
- To: "'foxboro@xxxxxxxxxxxxx'" <foxboro@xxxxxxxxxxxxx>
- Date: Tue, 15 Jan 2002 14:52:12 -0500
You will have to edit the /usr/fox/wp/bin/mk_glbls file,
and look for HSTNAME=$HIST . Change $hist in the historian name you want.
Patrick Den Haese
Senior System Service Engineer
Invensys Systems N.V./S.A.
phaese@xxxxxxxxxxx - Belgium
-----Original Message-----
From: Lowell, Tim: [mailto:tlowell@xxxxxxxx]
Sent: Tuesday, January 15, 2002 16:38
To: 'foxboro@xxxxxxxxxxxxx'
Subject: [foxboro] Default Alarm Historian in Alarm
Manager
We have FoxView and AIM*AT 3.02 at our site. When a WP
gets rebooted, or
the Alarm Manager gets restarted for some reason, the Alarm
Historian name
must be selected from the "Historian" button on the Alarm
History Display
(AHD). For the "Historian" button to work, you must have an
access level of
zero. We have recently decided to lock out the Console
Supervisors from any
access level zero functions. This means if a WP reboots in
the middle of the
night or on the weekends, the console guys have no access to
the AHD until
someone in the Control Group comes in and resets it for
them.
My question is, is their any way to tell the AHD what the
default historian
name is? I know I can change the "Historian" button to work
on a different
access level, which would solve the nights/weekends problem,
but I'd prefer
to go a step further and just tell the AHD what the correct
Historian name
is on boot-up, since we only have one Historian anyway. Has
anyone solved
this problem?
Tim Lowell
Control Systems Engineer
Phillips Petroleum Company, Trainer Refinery
Phone: 610-364-8362
Fax: 610-364-8211
tlowell@xxxxxxxx
___________________________________________________________________
This list is neither sponsored nor endorsed by The Foxboro
Company.
Use the information obtained here at your own risk. For
disclaimer,
see
http://www.thecassandraproject.org/disclaimer.html#maillist
list info: http://www.freelists.org/list/foxboro
subscribe:
mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
unsubscribe:
mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
___________________________________________________________________
This list is neither sponsored nor endorsed by The Foxboro Company.
Use the information obtained here at your own risk. For disclaimer,
see http://www.thecassandraproject.org/disclaimer.html#maillist
list info: http://www.freelists.org/list/foxboro
subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
Other related posts:
- » Re: [foxboro] Default Alarm Historian in Alarm Manager