Hello List We have configuration of AW51G running IA Batch V 8.1 (Unix) with CP40A/CP60 cluster on node bus with RCNI/NCNI combination. AW IA version V 7.1.1, WPs style B at 6.5.2 and one AW style B at 6.5.2. We are facing random CPs failure report at AW51Gwhich is default node bus master though CPs never failure actually. Look at its nfd_log files showed CRS error and cable faults. However when NFD master shifted to AW51B no CRS error and CP failures reported in the nfd_log file. Since IA Batch is running at AW51G we face lot of IA Driver error and many times batch manager got stopped. We already tried changing AW51G, new RCNI, tried different location for NCNI in 1X8 structure, replaced FO cable between RCNI & NCNI and those between 1X8 structures with new end terminators. But situation remain the same. It appears that node bus alarms in nfd_log with CRS errors due to version mismatches between both AW (7.1.1. and 6.5.2) as AW with 7.1.1 has/require faster diagnostic response compared to AW with 6.5.2. We tried workaround suggested by TAC to kill the nfd_8023 at AW51G but end up with all CPS actually failing ! Is there anyone faced similar problem and suggest work around. Best Regards G R OMPRAKASH _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave