Yes, you need to make sure the .DELTI?? parameter of the Sinking block is set
low enough to see the change you want to detect. It is only used for Peer to
Peer between CP's and not internally for connections of blocks in the same CP
Tom Vandewater
Control Conversions, Inc.
On Jul 6, 2017, at 9:52 PM, Goldie, Shaun S <Shaun.Goldie@xxxxxxxxxxxxxxxxxx>
wrote:
i had replicated blocks in a FCP so a noob could use notepad instead of good
old vi,
ive had an off list comment to check the delta on the sink given that 5 is a
big number for this value
it might be my problem
where i come from work is over for the week
Shaun
________________________________
NOTICE - This message and any attached files may contain information that is
confidential, legally privileged or proprietary. It is intended only for use
by the intended recipient. If you are not the intended recipient or the
person responsible for delivering the message to the intended recipient, be
advised that you have received this message in error. Any dissemination,
copying, use or re-transmission of this message or attachment, or the
disclosure of any information therein, is strictly forbidden. BlueScope Steel
Limited does not represent or guarantee that this message or attachment is
free of errors, virus or interference.
If you have received this message in error please notify the sender
immediately and delete the message. Any views expressed in this email are not
necessarily the views of BlueScope Steel Limited.
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company). Use the info you obtain here at your own
risks. See the disclaimer at www.thecassandraproject.org/disclaimer.html
foxboro mailing list: //www.freelists.org/list/foxboro
to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave