Per B0193AW, Rev L: SCI = 42: Platinum RTD (100 Ohm DIN 43760-1968) Material : Platinum Range : 0 to 620 deg C Curve : PR-238 (TI 5-26a) Duc -- Duc M. Do Dow Corning Corp. Carrollton Plant Carrollton, KY, US -----Original Message----- From: ZIEGLER, JOHN E [mailto:JEZIEGLER@xxxxxxxxxxxxx] Sent: Tuesday, February 25, 2003 10:05 AM To: Foxboro Mailing List (E-mail) Subject: [foxboro] My RTDs don't go below zero We have found that our RTDs don't read below zero. Is there some I/A or = instrument related issue that can explain this? Our RTDs are directly wired to an FBM03. The AIN block has an SCI of = 42. It has a scale configured to show -10 deg C to 150 deg C. We are = using 6.1.1 software. When the measured temperature is below 0 deg C, the block shows I/O bad. Thank you for your help. Jack Ziegler Sunoco Chemicals Frankford Phenol Plant Margaret & Bermuda Sts Philadelphia, PA 19137 215-537-2455 JEZiegler@xxxxxxxxxxxxx=20 ________________________________________________________________________ This email has been scanned for all viruses by the MessageLabs SkyScan service. For more information on a proactive anti-virus service working around the clock, around the globe, visit http://www.messagelabs.com ________________________________________________________________________ _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave