And don't forget these important rules: This appendix provides the procedure to upgrade CP30 or CP40 Control Processors to CP60 Control Processors on existing I/A Series systems. NOTE CP60 support for Fieldbus Cluster and Spectrum Migration products is presently limited to the V6.3.2 and V6.5 releases. The CP60 image (V6.4) supplied with the V6.4 and V7.0 releases does not support Cluster and Spectrum Migration products. Releases that use the V6.5 or later versions of CP60 software will provide support for Fieldbus Cluster and Spectrum Migration products. To upgrade CP30 or CP40 to CP60 on existing I/A Series systems: 1. Prior to replacing CP30 or CP40 control processors with a CP60, you must: install V6.3.2 or V6.5 and above System Software on the existing system and EEPROM all the FBP11/12/13/14 Integrators using the existing CP30 or CP40 based system. NOTE Be sure to EEPROM all the FBP11/12/13/14 Integrators as well as other FBMs using the existing CP30 or CP40 based system. If this step is not followed the CP60 replacement is not able to communicate with the older version FBP11/12/13/14 Integrator software: Old FBP EEPROM REV (Pre-V6.3.2 Systems) = 42.x New FBP EEPROM REV (V6.3.2 System) = 6.3.2 2. After the system has been upgraded to V6.3.2 or V6.5 and all the FBP11/12/13/14 Integrators have been upgraded with new IOM software, the CP30s and CP40s can be replaced with CP60 control processors. Follow the instructions in Control Processor 60 and Control Processor 60S Installation and Maintenance (B0400FB) for CP60 and DCM10E, DCM10Ef installation.-----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of Imran Butt Sent: Thursday, September 15, 2005 2:27 AM To: Foxboro Free List Subject: [foxboro] How to connect FBP10 on CP60 Dear All, We have and upgrade job of CP30 to CP60 and problem is the current system has CP30 with 100 series FBMs, FBI, FBC I/Os with FBP10. My query is can we connect CP60 to FBP10 through DCM10E because DCM10E simply convert the 2Mbps Fieldbus signal to 268kbps signal and FBP10 when connected to CP30 are with 268kbps Fieldbus. Best Regards, Imran Butt System Engineer IIImanstock Engineering Company (Pvt.) Ltd. 39-42 Farid Chambers, Abdullah Haroon Road Karachi - 74400, Pakistan Cell: +92-300-2353458 TEL: +92-21-5678952, 5678953, 5673145 FAX: +92-21-5682576 E-mail: <mailto:imran.butt@xxxxxxxxxxxxxxxxx> imran.butt@xxxxxxxxxxxxxxxxx URL: <http://www.manstock-engg.com/> http://www.manstock-engg.com _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave