Re: [foxboro] FW: LP02 printer online operation for alarms

  • From: "Boulay, Russ" <Russ.Boulay@xxxxxxxxxxxxxxxxxxxxxx>
  • To: "foxboro@xxxxxxxxxxxxx" <foxboro@xxxxxxxxxxxxx>
  • Date: Sat, 23 Apr 2016 14:25:15 -0400

Issue #2
Printer online offline usually occurs because Printer type is not correct or 
configuration issue.

Key files:

D:/etc/printers  (is correct type in that file)
D:/usr/fox/sp/files/cs_cfg/pars  (is correct type, port, etc..... correct in 
that file)

Lastly.....Device Monitor configuration.
Device Monitor could be marking the Printer as Failed and then Good as a 
destination...
This can be due to wrong type, current master may not have been committed so 
doesn’t have accurate system layout etc.....

D:/usr/fox/cs
Run dm_recon d  to create a cs_dm.current file on the current Device Monitor 
host

Who is the host?
/opt/fox/bin/tools/glof -p DEV_MONITOR  (to get the mac address of host)
Then fist AW's to find the mac address match.

If it matches the AW you are on ...then the cs_dm.current file will give you 
status

A dm_recon t from any AW will have that AW takeover as DevMon master.




-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On ;
Behalf Of Joseph M. Riccardi
Sent: Saturday, April 23, 2016 10:55 AM
To: foxboro@xxxxxxxxxxxxx
Cc: 'jesse.bolinger'
Subject: [foxboro] FW: LP02 printer online operation for alarms

Folks,


I am trying help a new member of our wonderful  <mailto:foxboro@xxxxxxxxxxxxx
foxboro@xxxxxxxxxxxxx users’ list support group; Jesse Bolinger.  For his 1st 
attempt, Jesse has 2 issues…





The 1st issue is his attempt to send an email and it is being garbled, see 
below.  I know others have had this same problem but I never did, so I am not 
sure of the fix.  Maybe it is just an issue with Hotmail but could someone help 
him fix this issue with his Hotmail account?

-----Original Message-----

From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On ;
Behalf Of Jesse Bolinger

Sent: Saturday, April 23, 2016 10:17 AM

To: foxboro@xxxxxxxxxxxxx

Subject: [foxboro] Fwd: LP02 printer online operation for alarms

« Ÿ*'z»§Š{h¶ ©®†åzj¬¦ëmŠx –)Þ¦¸§µêèžX§{ ­…# ¬ôázšâž×«,ý6Š䱫

?Mÿnëg¢Ö¥j¹¬ü‹Z¦—š®Ê¬~X§zéÝz»2²×¦™©ÚéžžßÆ¡ë(žX§yú+i÷°±ç(Û Ûaz{n®{+yÖ j)ÿ ‰ßŠ 
«jبžÌ ­çhêkzø¨ºÉrjwZ¦—š­Ê+­ç-ý»­v‰ÿ¶IèÂ'é®)íz·¯z¼(®GëZŠ[ÿK+-zoÈü 
ž®'¬ýh§vŒ,\ô¨~Ü ­ïÕz»"¢ ®)íz¿Î(ƒ"rº%Šwµó¯ÿ¦)Ï®)íz³Z™ïË?M’01ÿ ‹-yÖòXý4ÓoÀ[½ 
éåŠwš¶×¦¦Û





The 2nd issue is a problem he is having at a plant that is trying to start up 
but they need to resolve some Foxboro IA System issues 1st.  The email info he 
is trying to send to the list is below…

Has anyone  run into the problem of putting a line printer online with SMDH.

The printer LP02 works as LP02,  but not alarms.  It appears offline under 
system management.  Goes online for a few seconds and then turns red again.

Configurations were done previously and appear correct , but don't know if 
printer ever worked

Details:

System:  I/A Series,  Windows XP

Software:  Version 8

Printer: OKI Microline 186 9- pin

Printer Name:  LP02

SMDH: Hosted by WP0002- AW70NC

Online attempts= Goes online 10 seconds

SYSDEF: older and appears out of date.

IACC configuration:  Compound and blocks appear to be configured properly,  
with process  alarms directed to group 1.  Printer LP02 is defined as Item 4 in 
group 1.

Attempts/ results:

Windows  XP Test page = OK (attached)

IACC changes= OK

SYSMON messages= OK

Process Alarms= do not work as configured.

Thanks,

Jesse

Sent via my Samsung Galaxy, an AT&T 4G LTE smartphone





Welcome to the list, Jesse…





Joseph M. Riccardi

386-451-7607 Cell



 <mailto:Joe@xxxxxxxxxxxxx> Joe@xxxxxxxxxxxxx



"To give real service you must add something that cannot be bought or measured 
with money; and that is sincerity and integrity." - Donald A. Adams



From: Jesse Bolinger [mailto:jesse.bolinger@xxxxxxxxxxx]
Sent: Saturday, April 23, 2016 10:24 AM
To: Jesse Bolinger <jesse.bolinger@xxxxxxxxxxx>; Joseph M. Riccardi 
<Joe@xxxxxxxxxxxxx>
Subject: RE: LP02 printer online operation for alarms










_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric 
(formerly The Foxboro Company).  Use the info you obtain here at your own 
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html

foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave



______________________________________________________________________
This email has been scanned by the Symantec Email Security.cloud service.
______________________________________________________________________

*** Confidentiality Notice: This e-mail, including any associated or attached 
files, is intended solely for the individual or entity to which it is 
addressed. This e-mail is confidential and may well also be legally privileged. 
If you have received it in error, you are on notice of its status. Please 
notify the sender immediately by reply e-mail and then delete this message from 
your system. Please do not copy it or use it for any purposes, or disclose its 
contents to any other person.
 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own