Re: [foxboro] FCP270 failure

  • From: William C Ricker <wcricker@xxxxxxxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Tue, 25 Apr 2017 00:57:09 -0400

First of all, assumedly you know which of the pair has failed.  If not, the
6 character address printed on the
front can be correlated with your system management display to see.  Pull
the failed one and the running one
keeps going.

When you put a replacement unit in that slot, it talks to the running unit
and copies the running unit's EEPROM and 
running software, then starts up as shadow.  I don't remember if the fibers
should be connected before plugging it
in, or after, probably after.

Your shelf spare should be programed with letterbug NOSUCH.  That is
important if you are connecting a simplex FCP,
or the first side of a FT pair as it will send out a reboot request as soon
as it powers up. If you are plugging in an FCP 
as the second of an FT pair, like in this case, I think it doesn't matter.

The IP address, by the way,  is picked up from the boot host as part of the
reboot download.  

You mentioned the Reset button.  You can hit it on the failed side and it
should go thru some basic diagnostics, then
it should try to pull in the EEPROM and running software images.  

Pushing that button on the single running unit will cause a reset and a
reload process.  It will be off line 5 minutes or so. 
FBMs may go to fail-safe, as configured.  Block parameters take the values
at last checkpoint then initialize.

To understand this more thoroughly, may I recommend you  grab a chair and
the following two books, sit back and 
have a good read.

        B0700AR  DCP270 Users Guide
        B0700AG  FCP270/FCP280 Control Software Concepts

William C Ricker
FeedForward, Inc.

-----Original Message-----
From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On
Behalf Of Paul Brown
Sent: Monday, April 24, 2017 7:56 AM
To: foxboro@xxxxxxxxxxxxx
Subject: [foxboro] FCP270 failure

Hi.
We have a failed FCP270, it is one of a redundant pair and so installing a
replacement is not critical but important.
This is the first FCP failure we have encountered in the 6 or so years they
have been installed, we did have redundant CP30/40/60 which were simple to
replace.
We have one spare FCP270 which I am reluctant to install because I would
need to purchase a replacement.
I am tempted to press the 'Reset' button but not sure what would result.
Do these FCPs require a IP address to be programmed before they are
installed, we purchased a 'Pharos' device from Foxboro years ago to program
IP addresses but I think they are required for a FBM232.

Best regards
Paul

________________________________
Let's take care of the environment! Before printing this message, please
make sure it is really necessary. Recycle your PET bottles!

Registered Name: Lotte Chemical UK Ltd Place of Registration: England and
Wales Company Number: 7108602 Registered Office: Davies Offices, Wilton,
Redcar. TS10 4XZ

This communication is for use by the intended recipient and contains
information that may be privileged, confidential or copyrighted under
applicable law. If you are not the intended recipient, you are hereby
formally notified that any use, copying or distribution of this e-mail, in
whole or in part, is strictly prohibited. Please notify the sender by return
e-mail and delete this e-mail from your system. Unless explicitly and
conspicuously designated as "E-Contract Intended", this e-mail does not
constitute a contract offer, a contract amendment, or an acceptance of a
contract offer. This e-mail does not constitute a consent to the use of
sender's contact information for direct marketing purposes or for transfers
of data to third parties.

 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 


 
 
_________________________________________________________________________
This mailing list is neither sponsored nor endorsed by Schneider Electric
(formerly The Foxboro Company).  Use the info you obtain here at your own
risks.  See the disclaimer at www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:               //www.freelists.org/list/foxboro
to subscribe:           mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:        mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: