For about 10 years now we have been successfully using the pref command to assign buttons to the annunciator keypads on Unix WPs. Now when we try to add four new displays to four WPs, the results are very sporadic and unsuccessful. Out of four WPs in an area, we get different combinations of success - two out of four, none out of four, one out of four, etc. And different ones succeed on different WPs. We have tried re-editing the files many times and they certainly look ok pref -LBUG ascmd "loadalmpnl /usr/fox/alarms/01WP01AApan" I found this in the list archive, and when I did it, it verified with the correct display names: 2. In order to verify what is actually loaded into the alarm panel use the prtalmpnl command. Using the same configuration parameter from above LBUGAW01 and GCLBUGWP01 then the following command will dump the alarm panel contents to a file called 01WP01AApan.prt. in /usr/fox/alarms pref -LBUG ascmd "prtalmpnl" What now? We tried a reboot, still the same result. When we press the buttons that were not loaded correctly, the screen just flashes. Thanks, Virgil Loudermilk _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave