I don't like the garbage in my comparison so I'm going to try it again. AJ The following provides a brief comparison among ICC, FoxCAE, IACC, and IEE: Number of databases per system ICC: 1/CP FoxCAE: IACC: 1 / CP IEE: 1 Comments: IEE does not support by unit modularity for configuration. That is there is exactly one IEE server per system. IACC allows multiple servers per system, i.e., by unit modularity. Number of controllers per database ICC: 1 FoxCAE: IACC: 1-3 IEE: All Comments: IACC does not support putting everything in one database so peer-to-peer connections may need to be entered by hand. IEE does not have this limitation. ICC always requires by hand connection specification. Number of users per database ICC: 1 FoxCAE: IACC: 1 IEE: Many - limited by performance System Definition Support Built-in IEE: N FoxCAE: N IACC: Y (V6.4 and up) IEE: Y (V8.2 and up) Control Scheme Templates ICC: N FoxCAE: Y IACC: Y IEE: Y Graphical generation of control schemes ICC: N FoxCAE: N IACC: Y IEE: Y Animated Loop Drawings ICC: N FoxCAE: N IACC: Y IEE: Y HMI Building Integrated ICC: N FoxCAE: N IACC: Y IEE: N (On the roadmap for InFusion View, FoxView is TBD) Device Templates ICC: N FoxCAE: N IACC: Y IEE: Phase 2 FDT Support for FF ICC: N FoxCAE: N IACC: Y in IACC V2.2 IEE: Phase 2 FDT Support for HART/FoxCom ICC: N FoxCAE: N IACC: N IEE: N Comment: In all cases, FDM (PACTware) for HART and FoxCom is used InFusion Application Environment Support ICC: N FoxCAE: N IACC: N IEE: Y Scriptable Operation/Open database IEE: Y (ICC Driver Task) FoxCAE: Y (FoxPro Database) IACC: N IEE: Phase 2 (SQL Server used, but objects and object attributes are not necessarily accessible and the schema is not not published for external acces. Tools will be added to provide access to the data Workfile support: IEE: Y FoxCAE: Y (also keeps a separate database) IACC: Y (also keeps a separate database) IEE: N (Everything stored in SQL Server) Regards, Alex Johnson Invensys Systems, Inc. 10900 Equity Drive Houston, TX 77041 713.329.8472 (voice) 713.329.1700 (fax) 713.329.1600 (switchboard) alex.johnson@xxxxxxxxxxxxxxxx Confidentiality Notice: =0AThe information contained in this electronic m= essage and any attachment(s) to this message are intended for the exclusi= ve use of the recipient(s) and may contain confidential, privileged or pr= oprietary information. If you are not the intended recipient, please noti= fy the sender immediately, delete all copies of this message and any atta= chment(s). Any other use of the E-Mail by you is prohibited.=0A _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave