Dear all, I just ran into a problem: we need to add a FBM204 to our system, which is I/A 7.0 with 4 pairs CP60 and six AW51/WP51(Sun Blade 150) stations. Before we added the FBM204, the system has no other FBM204 installed. We added a ECB2 and configured it as HWTYPE=204, SWTYPE=2. AIN and AOUT were added and configured. The status of ECB2 was ONLINE and ON_SCAN. The problem is when we checked the AIN and AOUT block, the AIN block was indicated as BAD I/O even the transmitter outside worked normally. When we set output of AOUT as 50%, no milliampere can be measured. We also added a FBM241C to our system, and it works fine once it was added. The difference is there are FBM241C already used in system. My question is: 1. Does it matter that there are same type FBM already installed in system? So the newly added modules can be recognized by system? 2. Is there any thing special about adding FBM204 to system? 3. What can I do to probably solve the problem? Thanks in advance for your precious time for reading this and any help is appreciated. _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave