We have had several failures recently of legacy FBMs of different types. They fail red/green and the message is loss of communication. We found that in almost all cases, that the FBM letterbug needed to be reseated or replaced to get the FBM to work again. These FBMs have been in service for 6 to 7 years. These FBMS are installed in 1X8 FBM racks inside Rittal cabinets in an air conditioned environment. During our recent outage we checked the nosecone and letterbug of all of our FBMs. While pushing on the letterbug we had 12 FBM's (out of about 400) reboot. Have any others on the list experienced this? If so, what have you done to correct it? Thanks, Jim Kahlden jkahlden@xxxxxxxx Lower Colorado River Authority Fayette Power Project 6549 Power Plant Road La Grange, TX 78945 (979) 249-8514 (Ph) (979) 249-8390 (Fax) _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave