Re: V8 on Nodebus V8 equipment must be connected to the Mesh network; it cannot attach to a Nodebus based network. = The Nodebus is standard A/B redundant network and each station attached to it presents a network interface with the same MAC address on both the A and B sides. The Mesh network has a totally different approach to networks; it weaves the switches together such that there are multiple paths between any two stations. As you might imagine, the communication software is different on the Mesh than on the Nodebus. Re: FV 10 on V7.1.1 It will not work. Regards, Alex Johnson Invensys Systems, Inc. 10900 Equity Drive Houston, TX 77041 713.329.8472 (voice) 713.329.1700 (fax) 713.329.1600 (switchboard) alex.johnson@xxxxxxxxxxxxxxxx -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of David Johnson Sent: Tuesday, June 26, 2007 1:55 PM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] What version is what? Hi guys, This may be quite obvious, but I am still seeking clarification. I am needing to load a graphics testbed, and would like to be able to temporarily replace an I/A version 6.2 NT workstation using a DNBT connection, with an XP workstation running Foxview/FoxDraw 10.1. (This will be goin MESH later this year.) The FoxView/FoxDraw CD says for 8.X systems. Can I connect an 8.X system to a nodebus via DNBT or is it strictly MESH. If so, will FoxDraw v10.1 run on an I/A v 7.1.1 PC although it's not "officially" supported. Thanks, David -- = "For my next trick I'll need a volunteer." = = _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html = foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave = Confidentiality Notice: The information contained in this electronic message and any attachment(s) = to this message are intended for the exclusive use of the recipient(s) and = may contain confidential, privileged or proprietary information. If you are= not the intended recipient, please notify the sender immediately, delete a= ll copies of this message and any attachment(s). Any other use of the E-Mai= l by you is prohibited. _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave