[foxboro] Upgrade from 6.4 to 6.5.2 causes pulse rate values to double
- From: Mark Dumond <mdumond@xxxxxxxxxxxxxx>
- To: foxboro@xxxxxxxxxxxxx
- Date: Mon, 12 Sep 2005 15:32:18 -0400 (EDT)
I wanted to pass this warning on to those who may be in the process of
upgrading I/A versions.
Problem: After upgrading from 6.4 to 6.5.2, all AIN references to pulse inputs
on FBM-06s (SCI=8) show values that are double what they really should be.
Temporary fix: We put a KSCALE of 0.5 for now.
This problem has only been recently identified by Foxboro.
Mark Dumond