List, Can anyone tell me how and what to set on a REALM block to make the ROC work? In the past I have set up on a test bed and used a RAMP block to test but it never works as I think it should. I want an alarm to be generated when the temperature goes up 500 DegF in 5 minutes. The temp normally operates at a constant value but if it increases by the 500 Degrees within 5 minutes then I want an alarm. In the past I have accomplished this by building two AIN blocks and changing the "period" on one and sending these to a REALM block (MEAS & DEVSPT). One problem I have now is there is no period with a 5 minute execution. Besides if I could configure the REALM correctly I would only have to create one block instead of two. Anyone with any ideas? Michael L. Jaudon TRONOX, LLC (Technology Group-Hamilton, MS) (662)343-8710 Office (662)304-0313 Cell mike.jaudon@xxxxxxxxxx If you are not the intended recipient of this e-mail message, any use, distribution or copying of the message is prohibited. Please let me know immediately by return e-mail if you have received this message by mistake, then delete the e-mail message. Thank you. _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave