Re: [foxboro] 3 CHARC blocks cascaded

  • From: "Joerg Wierz" <jwierz@xxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Wed, 19 Mar 2003 17:08:25 +0100

Hi, you didn't get any answers because you didn't describe your problem
completely (include top and bottom of your information stream !). What do
you want to do? If you want to maipulate a measurement you don't need any
backcalculation (forget about BCALCI/O, PRIBLK=0). If you want to adapt a
nonlinear valve characteristic in a control loop or somehing like that, then
you should implement back calculation, but you'll also have to take your
AOUT and PID block into the boat.

     PID                       CHARC             AOUT
     OUT   -------> MEAS         OUT   -------> MEAS
     BCALCI<----- BCALCO   BCALCI<-----BCALCO

     PRIBLK=0        PRIBLK=1          PRIBLK=1

Add as many CHARC's inbetween as you like.

J.Wierz
----- Original Message -----
From: "Tamer Ahmed" <tmahmoud1973@xxxxxxxxx>
To: <foxboro@xxxxxxxxxxxxx>
Sent: Sunday, February 09, 2003 10:07 AM
Subject: [foxboro] 3 CHARC blocks cascaded


>
> we have about 56 points and we want to build 3 CHARC
> blocks in cascade
> we are using I/A 6.2.1 and we are trying to build
> these CHARC blocks by connecting the 3 CHARC blocks as
> follows:
>
>    CHARC1           CHARC2             CHARC3
>
>     OUT   -----> MEAS     OUT   -----> MEAS
>     BCALCI<----- BCALCO   BCALCI<-----BCALCO
>
>     PRIBLK=0        PRIBLK=1          PRIBLK=1
>
> but with these connections we the cascade loop are
> open. any one can help
>
>
> __________________________________________________
> Do you Yahoo!?
> Yahoo! Mail Plus - Powerful. Affordable. Sign up now.
> http://mailplus.yahoo.com
>
>
> _______________________________________________________________________
> This mailing list is neither sponsored nor endorsed by Invensys Process
> Systems (formerly The Foxboro Company). Use the info you obtain here at
> your own risks. Read http://www.thecassandraproject.org/disclaimer.html
>
> foxboro mailing list:             //www.freelists.org/list/foxboro
> to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
> to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
>
>

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: