[foxboro] RE : Master Timekeeper Disabled

  • From: "Doucet, Terrence" <tdoucet@xxxxxxxxxxxxxxxxxx>
  • To: <foxboro@xxxxxxxxxxxxx>
  • Date: Thu, 2 Aug 2007 12:12:17 -0400

Change it in any AW you want (or a WP that is a System monitor WP for that AW) 
and that AW will become the master.  If you want to find out the current master 
and you have smon_log enabled on all stations with a System Monitor, then cat 
the smon_log and grep for   keeper   and look for the last line (most recent 
date, time)  with  "Master Timekeeper now Enabled"
 
 
Terry
________________________________

De: foxboro-bounce@xxxxxxxxxxxxx de la part de David Vergara S. (SANTAFE - CMPC 
Celulosa)
Date: jeu. 2007-08-02 11:58
À: foxboro@xxxxxxxxxxxxx
Objet : Re: [foxboro] Master Timekeeper Disabled




We have a lot of AWs.
How can We identify in wich AW we have to change the Time?

-----Mensaje original-----
De: foxboro-bounce@xxxxxxxxxxxxx =
[mailto:foxboro-bounce@xxxxxxxxxxxxx]En
nombre de Ali Ahmed
Enviado el: S=E1bado, 07 de Julio de 2007 3:42
Para: foxboro@xxxxxxxxxxxxx
Asunto: Re: [foxboro] Master Timekeeper Disabled


=20
Explore your SMDH (Sys_Mgmt), click TIME and then set the time and hit
RETURNSET.=20

Rgds,=20

Ali Ahmed Zahidi


------------------------------------------------------------------------=
----
From:  JSpence224@xxxxxxx
Reply-To:  foxboro@xxxxxxxxxxxxx
To:  foxboro@xxxxxxxxxxxxx
Subject:  [foxboro] Master Timekeeper Disabled
Date:  Fri, 6 Jul 2007 16:17:44 EDT
>
>Hello All,
>
>
>We are currently using I/A Release 7.0 on our site and our alarm =
printer
>keeps filling up with "Master Timekeeper disabled" alarms. The =
complete
printed
>text is as follows :
>
>
>SYSMON =3D CGSM02  CGAW01  Process =3D mt_task
>SYSMGM 000026 Master Timekeeper disabled - use SYS_MGMT to set  =
date/time
>
>
>and :
>
>
>
>SYSMON =3D CGSM01  CGAW02  Process =3D mt_task
>SYSMGM 000026 Master Timekeeper disabled - use SYS_MGMT to set  =
date/time
>
>
>These alarms come in every 20 minutes. The date and time has been set=20
before
>but we still have the alarms filling up our print outs. The indicated  =
time
>on our graphic display screens seems to be correct and the date is =
also
>correct. Not sure what the problem is. Has anyone else seen this =
problem
before?  Do
>I have to set the date and time in more than one place?
>
>
>Any help or hints will be greatly appreciated.
>
>
>Thank you in advance.
>
>
>Jim Spence
>
>Controls Engineer
>Procter &Gamble
>Oxnard Site
>
>
>
>
>
>************************************** See what's free at
http://www.aol.com <http://www.aol.com/> .
>
>
>
>
>_______________________________________________________________________=

>This mailing list is neither sponsored nor endorsed by Invensys =
Process
>Systems (formerly The Foxboro Company). Use the info you obtain here =
at
>your own risks. Read =
http://www.thecassandraproject.org/disclaimer.html
>
>foxboro mailing list:             =
//www.freelists.org/list/foxboro
>to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
>to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
>


------------------------------------------------------------------------=
----
Don't just search. Find. MSN Search[1] Check out the new MSN Search!=20

--- Links ---
   1 http://g.msn.com/8HMAEN/2749??PS=3D47575
=20
=20
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
=20
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Djoin
to unsubscribe:      =
mailto:foxboro-request@xxxxxxxxxxxxx?subject=3Dleave
=20


_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html

foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave




-- No attachments (even text) are allowed --
-- Type: application/ms-tnef
-- File: winmail.dat


 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: