We are upgrading from v.8.4.2 to v8.7 at one of our sites, and we've found out that as soon as you put a v.8.7 box on the MESH, all the other v.8.4.2 machines lose their Common Alarm Group functionality. This makes for some very unhappy console operators who have to silence each alarm at every console in the group, right in the middle of a very stressful shutdown. Luckily, we have a small army of Invensys folks on site, and one of them unearthed QF1047977b from deep in the bowels of the support web site (after another two service guys and I missed it). This has (we think) fixed the problem, at least as of now. This is EXACTLY the same problem that happened when you upgraded from v.8.2, 8.3, 8.4, 8.4.1 or 8.4.2 to v.8.4.3. You would think someone at Invensys would test this and fix it before they released v8.7, or at least check it and let us know in the v.8.7 release notes. You would be wrong. A customer had to discover this problem and create a CAR, and this QF was released on 4/2/12. Of course, you can't download it from the usual QF search page. The Invensys guy did an unorthodox search and happened to find it on a totally different page. Happy upgrading! Thanks, Tim Lowell Tesoro _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave