Sorry that is DI15 On 9/12/07, Imran Waheed Butt <butt.imran@xxxxxxxxx> wrote: > > Dear Kevin, > > Sorry there there was not MG30 that is COMM15 we were using now that is > replaced by FBM231. > > Thanks and Regards, > Imran > > > On 9/12/07, Kevin Fitzgerrell <fitzgerrell@xxxxxxxxx> wrote: > > > > Imran, > > > > How are you using an MG30 to communicate with an AB PLC? Are you > > using a Prosoft card? > > > > Regards, > > > > Kevin FitzGerrell > > > > On 9/12/07, Imran Waheed Butt <butt.imran@xxxxxxxxx> wrote: > > > Dear All, > > > Our customer is upgrading the I/A version form V4.3 Unix to V8.2 on XP > > and > > > previous system has CP30FT communicating with 100 series FBMs and FBCs > > and > > > quantity 3 MG30 gateways communicating with Allen Bradley PLC through > > CAM or > > > Modem which is provided by Allen Bradley. > > > > > > The CP30FT is upgraded to FCP270FT and 100 series FBM and FBC are > > remain > > > same. > > > > > > The 3 no. MG30 are replaced by and other FCP270FT with FBM231 (FT). > > > > > > I am at the commissioning/installation of the system and facing > > following > > > problems, > > > > > > 1. FBM231 is not communicating with AB PLC through CAM or Modem as > > we > > > translate the same DIP switch setting which is on the P0970VN (MG30 > > > configuration selection switch) to the FBM231 TA, the switch > > settings are > > > as, > > > MG30>>> SW1-1,2,3,4,7,8 & SW2-1,3,4,6,8 are closed and > > > remaining are open > > > we translate them form documents B0193RL-Rev H page 49-50 and form > > > B0700AH Rev E page 62-63 and translated switch setting are as, > > > FBM231 TA>>> A-2,4,6,8 & B-4,8 & C-1 are close and > > > remaining are open. > > > But it is not communicating with PLC. > > > 2. The cable part number which is connecting PLC to Gateway is > > > P0970WY-C and we are using the same cable. > > > 3. Previously AIN, AOUT, CIN and COUT blocks are in the database of > > > MG30 which communicate with PLC, and now these blocks we can't use > > with > > > FBM231 to communicate with PLC so, we create RIN, ROUT, BIN and BOUT > > blocks > > > and connect the out put of these blocks to the input of AIN and CIN > > and > > > output of COUT and AOUT to input of BOUT and ROUT. > > > Now problem is that the previous addressing of PNT parameter of CIN > > is > > > and COUT are like 4.12:0 and 16.15:0 and for AIN and AOUT have like > > > 126:0 at their PNT parameter. Kindly guide me how to translate the > > above > > > format to PNT parameter to the format of BIN,BOUT, RIN and ROUT. > > > We copy the same PNT no. to the PNT of BIN, BOUT, RIN, ROUT's PNT > > but > > > when loaded to FCP it gives error W65. > > > > > > Kindly all the experts provide me solution of above issues. > > > > > > > > > > > > Thanks and Best Regards, > > > > > > Imran Butt, > > > > > > System Engineer, > > > > > > Manstock. > > > > > > > > > > > > _______________________________________________________________________ > > This mailing list is neither sponsored nor endorsed by Invensys Process > > Systems (formerly The Foxboro Company). Use the info you obtain here at > > your own risks. Read http://www.thecassandraproject.org/disclaimer.html > > > > foxboro mailing list: //www.freelists.org/list/foxboro > > to subscribe: mailto: foxboro-request@xxxxxxxxxxxxx?subject=join > > to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave > > > > > > > -- > Thanks and Best Regards, > Imran Butt > System Engineer > Manstock Engineering Company (Pvt.) Ltd. > 39-42 Farid Chambers, Abdullah Haroon Road > Karachi â?? 74400, Pakistan > Cell: +92-321-2102686 > Home: +92-21-4590568 > Office: +92-21-5678952, 5678953, 5673145 > FAX: +92-21-5682576 > E-mail: butt.imran@xxxxxxxxx > URL: http://www.manstock-engg.com -- Thanks and Best Regards, Imran Butt System Engineer Manstock Engineering Company (Pvt.) Ltd. 39-42 Farid Chambers, Abdullah Haroon Road Karachi â?? 74400, Pakistan Cell: +92-321-2102686 Home: +92-21-4590568 Office: +92-21-5678952, 5678953, 5673145 FAX: +92-21-5682576 E-mail: butt.imran@xxxxxxxxx URL: http://www.manstock-engg.com _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave