How many FBM's do you have on this fieldbus? Is it your I/O load in the station block that has increased considerably? More DCM's will drop the I/O load considerably. -----Original Message----- From: foxboro-bounce@xxxxxxxxxxxxx [mailto:foxboro-bounce@xxxxxxxxxxxxx] On Behalf Of Jaime Claramunt R. (Inforsa) Sent: Friday, October 21, 2005 7:58 AM To: foxboro@xxxxxxxxxxxxx Subject: [foxboro] CP60 and FBM legacy Hey List... We recently upgraded one of our 10 CP40A-FT to CP60FT. (well, with all net changes required... V7.x, FO switches, etc) We found a prob here... CP60 new loads are very high... control loads... running at 0.5s , it's reaching 112% and 44% (phase 0,1). Worse than our old CP40... We used one pair of DCM to interfase new CP60 and existent legacy fieldbus (3 remote racks, pair of PIO each) We are working with our local reps. but not too much clues yet... Does anybody has some hints ?? Thx. Regards, Jaime Claramunt INFORSA Paper Mill CHILE _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave _______________________________________________________________________ This mailing list is neither sponsored nor endorsed by Invensys Process Systems (formerly The Foxboro Company). Use the info you obtain here at your own risks. Read http://www.thecassandraproject.org/disclaimer.html foxboro mailing list: //www.freelists.org/list/foxboro to subscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=join to unsubscribe: mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave