Hi Joachim,

I will answer you although it probably doesn't help much!
My experience has always been that increasing MAX_ACTIONS works, on both NT
and UNIX, in init.user.
So, here are some obvious things, maybe you overlooked one....

- Did you reboot?
- Did you remove the # in front of MAX_ACTIONS
- Did you perhaps add you "own" MAX_ACTIONS and is it overwritten later in
the file?
- Even more stupid suggestion: Did you perhaps changed init.user.rel in
stead of init.user?

You say the panels do not work "correctly". Do they work at all? Do they
only work for blocks 1-2000? Are there any syntax errors in your AAtab
files?

As a last resort: You could try to change MAX_ACTIONS in wp51_glbls, however
this has never been necessary in my experience, besides its "illegal". (own
risk etc)

Good Luck,
Bram Marsman
Invensys Systems Netherlands.

-----Original Message-----
From: JL Joachim Leuker [mailto:Joachim_Leuker@xxxxxxxxxxxxxxxxx]
Sent: donderdag 31 oktober 2002 9:42
To: 'foxboro@xxxxxxxxxxxxx'
Subject: Re: [foxboro] Alarm panel



Hello, folks,

the discussion about language and time of day is quite interesting, but =
for
me an answer to my question would even be more helpful.

Does this work in all of your I/A systems? No idea?

Answer in German or French is no problem! :-)

Regards,
Joachim Leuker

-----Urspr=FCngliche Nachricht-----
Von: JL Joachim Leuker [mailto:Joachim_Leuker@xxxxxxxxxxxxxxxxx]
Gesendet am: Dienstag, 29. Oktober 2002 10:21
An: foxboro@xxxxxxxxxxxxx
Betreff: [foxboro] Alarm panel


Hi, list,

one of our clients reports problems with the operation of Alarm Panels.

If the ...AAtab file is longer than about 50kB (about 2000 lines) the =
panels
do not work correctly. So they changed MAX_ACTIONS in init.user to a =
higher
value, but without success. It looks like 2000 is the default value.

The system is NT based mixed of V.6.3 and V.6.2.1 with 2 panels on each
station. 6 stations form a common alarm group. All stations have the =
same
init.user entry and the same AAtab file. One of the stations has a =
software
panel (FoxPanels) on the screen.

Any hints why the panels are confused by the longer AAtab files?

Thanks for attention
Joachim Leuker

--
Dr. Joachim Leuker - Client Manager
Actemium - HMS Planung & Automation GmbH
Duisburg, Germany
http://www.actemium.de
ACTEMIUM - A BRAND OF GTIE

 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 
 
 
_______________________________________________________________________
This mailing list is neither sponsored nor endorsed by Invensys Process
Systems (formerly The Foxboro Company). Use the info you obtain here at
your own risks. Read http://www.thecassandraproject.org/disclaimer.html
 
foxboro mailing list:             //www.freelists.org/list/foxboro
to subscribe:         mailto:foxboro-request@xxxxxxxxxxxxx?subject=join
to unsubscribe:      mailto:foxboro-request@xxxxxxxxxxxxx?subject=leave
 

Other related posts: